background image

                                                           

HWHC2100 v2.53 Operation Manual     

CONFIDENTIAL

 

 

 

 

21 Harbor Park Dr. N, Port Washington, NY 11050 Phone: 516.626.72211 Fax: 516.626.7201 

12 

Point the Valve shell be close. 

Range: 40

°

F to 220

°

F with 1

°

F steps. Default value is 70°F

.

 

SysCutOffTem 

System Water Temperature Cut Off Set Point. If System Water Temperature above the Cut Off Set 
Point the Valve shell be close. 

Range: 40

°

F to 220

°

F with 1

°

F steps. Default value is 90°F

.

 

 
MaxWaterTemp 

Maximum allowed  water temperature.  If calculated Target temperature exceeds  

MaxWaterTemp

 the controller in 

AUTO

 mode will maintain the water temperature at 

MaxWaterTemp.

  

 

Range: 170°F to 250°F with 1° step. Default value is 250°F. 

 
 
MinWaterTemp 

Defines minimum water temperature in the system.  Used only in the AUTO mode of operation. 
The controller calculates the Target water temperature based on the outdoor temperature, heat gain, 
and the compensator value and controls burner or valve to hold either the calculated temperature, 
or the MinWater Temperature, whichever is higher. 

Range: 70°F to 170°F with 1° step. Default value is 140°F. 

 
 
PumpRunDelay 

 Sets the time to run the System Pump for a longer period of time after the boiler has been turned 
off or the valve has been closed. This feature allows for dissipating the excess heat from the boiler 
combustion chamber and prevent the boiler from overheating. 

Range: 0 to 99 minutes with 1-minute step. Default value is 2m. 

HeatUp Time 

The heat-up time is designated to return the building temperature  to its Day heat level after Night 
heat level. 

Range: 0 to 99 minutes with 1-minute step. Default value is 30minutes.

 

Motor Pause 

In AUTO and SET mode of operation specify the appropriate time (in seconds) between the Valve 
(Motor) motion. Normally, this parameter is set at the system installation time.   
Range: 0 to 127 seconds with 1 second step. Default value 30sec.

 

VlvCtrl Type 

Defines Type of Control Interface to the motorized Valve. 
There are three possible Type of Control Interface to the motorized Valve 
implemented on the controller: 

-

 

Relays; 

-

 

Current Loop (4ma-20ma);

 

-

 

Potentiometer.

 

o

 

Default Interface = Relay

.

 

Motor Type 
 

There are 8 types of motors (dependent on the time duration of valve close position to the open 
position) from 2minutes to 9 minutes with increment of one minute. 

Type 2m – for time duration 

of 2 minutes; Type 3m – for time duration of 3 minutes, and so on

Default value is 3m. 

TIME & DATE 

Current Year, Month, Day, and Time can be entered and adjusted. The "am/pm" displayed with 
capital letters when Daylight Saving Time is in effect. 

 
Com.ID 

Each HWHC2100 connected to the local server via the RS485 bus. To establish proper connection 
the controller should have a unique communication address (ID). 

Range: 1 to 99. 

 
 

8. System Status Information 

 
All operational parameters and useful information can be seen on the low line of the LCD display by using Up/Down 
and Enter keys (see Fig.2 left corner). The following information can be selected for displaying on the lower line of the 
LCD: 
 

Information 

Example 

Description 

Valve Position and 
System Temperature 

(or Return Temperature) 

    VLV =16% 

ST = 152°  

                

or 

    VLV =24% 

RT = 175°

 

Current valve position as percent of the Open status and 
Hot water heating system temperature at the RTD sensor 
(="fail" if temperature sensor malfunction). 

Return Temperature  

(or System Temperature) 

       Ret Temp = 60.4°  

               or 

      Sys Temp = 123.5° 

Condensate return temperature at the RTD sensor. 
If sensor not installed or not use: (“RtnTempSr-NotUse”), 

If the sensor  malfunction: (="fail") 

Summary of Contents for HWHC2100

Page 1: ...temperature or condensate return temperature return water temperature HWHC2100 works as a standalone controller and can be connected to a Local Server which provides additional parameters adjustments...

Page 2: ...es or change settings The control keypad consists of four pushbuttons Escape Esc Down Up Enter Enter The keys are also marked with letters A B C D used to simplify the passwords memorizing During norm...

Page 3: ...ened or closed depending on the mode of the last operation as follows Operation Mode Valve Direction Status Information AUTO To Close Position Sync_C M_SET To Close Position Sync_C M_CLOSE To Close Po...

Page 4: ...d then one should enter a certain key sequence For convenience the passwords are coded as the sequence of letters e g DDBBCBA Starting point of the menu is the topmost item of the leftmost box current...

Page 5: ...s SET TIME DATE SET Minute NEWMinute 56 VlvCtlType Curnt SET Com ID NEW Com ID 3 SET Hour NEW Hour 2PM D Mild 55 F CACADCB SET Month NEW Month 02 N Mild 45 F SET MAINTENANCE Password1 SET D Mild NEW D...

Page 6: ...h between the different configuration one should press Up or Down keys Hitting Enter key accepts the new configuration Esc rejects and leaves the configuration unchanged 6 Modes of operation The upper...

Page 7: ...he NIGHT MILD WEATHER and NIGHT SETBACK parameters Please see an example in section 6 Notes The valve will be unconditionally set to 0 when Out Door Temperature achieves Day time Mild Weather Set Poin...

Page 8: ...Fig 3b With any of the ratios the colder it becomes outside the hotter the temperature of the system water On the both examples Compensator 0 and NIGHT SETBACK 0 Positive Compensator values shift the...

Page 9: ...g 4 illustrates effects of the Compensator on the control curve Range 40 F to 40 F with 1 step Default value is 0 F D Mild DAY MILD WEATHER The controller closes the valve completely when the outdoor...

Page 10: ...ens 10 Boost Span Morning boost time span The controller boosts heat only with AUTO mode in effect Range 0 30 60 90 120 minutes 0 means no boost or Vari Boost the length of the Boost time depends on t...

Page 11: ...d from host computer is higher than this set point and the time is between Day End and Day Begin then the valve will be closed completely N ICOFF state Range 40 to 80 F InDrD_Band Used along with In D...

Page 12: ...de of operation specify the appropriate time in seconds between the Valve Motor motion Normally this parameter is set at the system installation time Range 0 to 127 seconds with 1 second step Default...

Page 13: ...ration Valve position is 37 open System temperature is 144 F Morning Heat Up Calculated Target Temperature is 188 F AUTO 189 BOOST AUTO 140 D Mild AUTO 140 N Mild VLV 37 ST 155 VLV 12 ST 144 VLV_0 ST...

Page 14: ...ign will change to Mode of Operation OFF Mode of Operation M_SET SET 180 VLV 67 ST 123 Target Temperature is 180F Normal operation system temperature is 123F For the motorized valve controlled by rela...

Page 15: ...adjustment valve position would perform at the close position Pump would be turn off after period of time set by the Pump Run On set point System Temperature Sensor fails Initial Synchronization Valv...

Page 16: ...and shows actual reading of the temperature sensor ST zz x 3 The lower line of the display shows possible adjustment for example NewSysTAdj 0 2 4 Press Up or Down key to make the reading equal to the...

Page 17: ...MCI Transformer 4 06 7345 1 5 10 9 7 6 Pump1 2 Pump1 1 Pump2 1 Pump2 2 9 5 12 4 8 13 14 Terminals Board J1 1 2 3 H H 8 9 10 11 12 13 14 7 4 5 6 1 2 J2 1 2 Transformer 1 9 5 4 8 9 5 Motor Controls comm...

Reviews: