AUTO: 

The controller provides automatic valve positioning in accordance with the measured temperatures, 
season, time of the day, and the selected parameters. This mode is designed to be the main mode of 
operation. If the system parameters are set properly, then there is no need in manual intervention in 
the system performance virtually at any weather condition. The HWHC2100 is capable to keep 
calculated target temperature in parameters set by ‘D_Band’ set point. 

In AUTO mode the controller distinguishes four day periods (Fig.6): 

1.

 

The morning heat-up period

 starts at the‘

DAY BEGIN’ 

Set Point. During this period the 

controller changes the valve position from nighttime to daytime temperature values with a 
constant rate. The heat-up time span is variable form 0 to 100 minutes (with step of 1 minute).    

2.

 

The morning boost period

 begins immediately after the morning heat-up period ends. The   

‘BOOST SPAN’ and ‘BOOST ADVANCE’ parameters define the boost duration and its 
amount.  

3.

 

Normal daytime operation 

begins from the Boost period end to ‘

DAY END’ 

Set Point. 

4.

 

Nighttime period

 (‘

DAY END’

 to ‘

DAY BEGIN’

). The amount of delivered heat can be 

reduced against the daytime period, as defined by the’ NIGHT MILD WEATHER’

 

and 

‘NIGHT SETBACK’ parameters. (Please see an example in section 6). 

Notes:  

The valve will be unconditionally set to 0% when: 

- Out Door Temperature achieves  Day time Mild Weather Set Point (at Day Time) or Night  

    Mild Weather Set Point (at Night time); 

- Apartments temperature (Indoor Temperature) average supplied from host computer highest  

       then Indoor Temperature CutOff  (Day/Night)set Point plus D_Band.  

 - If  Return Water Temperature(or System Water Temperature) above the Cut Off Set Point 

- If current date is between the Winter End and Winter Begin settings (Summer time). 

 M_SET: 

(Manually Set 
Temperature) 

 

In this mode the HWHC2100 automatically keeps the Supply (System) Hot Water Temperature (or 
Return Water Temperature) at the set point entered by operator within a dead band zone set by 
‘D_Band’ parameter. (In case the outdoor sensor failed in AUTO mode, the HWHC2100 
automatically switches to this mode of operation). 

    M_OPEN: 

(Manually Open) 

M_CLOSE:

 

(Manually 
Close) 

These modes can be used in emergency to open or close the valve fast and completely regardless of 
the valve position.  

The M_OPEN unconditional opening of the valve and turning pump on (if it was off).  

The M_CLOSE unconditional closing of the valve. After valve close the pump will stay on for a 
period of 2 seconds and will turn off.     

 

 
To change the mode, select 

SET OPER MODE

 item in the menu, press 

Enter

, then, with 

Up

 or 

Down

 key select a 

new mode, and press 

Enter

. When the M_SET mode is selected, the new temperature value (‘MTGTemp’) must be 

entered. 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for HWHC2100

Page 1: ...temperature or condensate return temperature return water temperature HWHC2100 works as a standalone controller and can be connected to a Local Server which provides additional parameters adjustments...

Page 2: ...es or change settings The control keypad consists of four pushbuttons Escape Esc Down Up Enter Enter The keys are also marked with letters A B C D used to simplify the passwords memorizing During norm...

Page 3: ...ened or closed depending on the mode of the last operation as follows Operation Mode Valve Direction Status Information AUTO To Close Position Sync_C M_SET To Close Position Sync_C M_CLOSE To Close Po...

Page 4: ...d then one should enter a certain key sequence For convenience the passwords are coded as the sequence of letters e g DDBBCBA Starting point of the menu is the topmost item of the leftmost box current...

Page 5: ...s SET TIME DATE SET Minute NEWMinute 56 VlvCtlType Curnt SET Com ID NEW Com ID 3 SET Hour NEW Hour 2PM D Mild 55 F CACADCB SET Month NEW Month 02 N Mild 45 F SET MAINTENANCE Password1 SET D Mild NEW D...

Page 6: ...h between the different configuration one should press Up or Down keys Hitting Enter key accepts the new configuration Esc rejects and leaves the configuration unchanged 6 Modes of operation The upper...

Page 7: ...he NIGHT MILD WEATHER and NIGHT SETBACK parameters Please see an example in section 6 Notes The valve will be unconditionally set to 0 when Out Door Temperature achieves Day time Mild Weather Set Poin...

Page 8: ...Fig 3b With any of the ratios the colder it becomes outside the hotter the temperature of the system water On the both examples Compensator 0 and NIGHT SETBACK 0 Positive Compensator values shift the...

Page 9: ...g 4 illustrates effects of the Compensator on the control curve Range 40 F to 40 F with 1 step Default value is 0 F D Mild DAY MILD WEATHER The controller closes the valve completely when the outdoor...

Page 10: ...ens 10 Boost Span Morning boost time span The controller boosts heat only with AUTO mode in effect Range 0 30 60 90 120 minutes 0 means no boost or Vari Boost the length of the Boost time depends on t...

Page 11: ...d from host computer is higher than this set point and the time is between Day End and Day Begin then the valve will be closed completely N ICOFF state Range 40 to 80 F InDrD_Band Used along with In D...

Page 12: ...de of operation specify the appropriate time in seconds between the Valve Motor motion Normally this parameter is set at the system installation time Range 0 to 127 seconds with 1 second step Default...

Page 13: ...ration Valve position is 37 open System temperature is 144 F Morning Heat Up Calculated Target Temperature is 188 F AUTO 189 BOOST AUTO 140 D Mild AUTO 140 N Mild VLV 37 ST 155 VLV 12 ST 144 VLV_0 ST...

Page 14: ...ign will change to Mode of Operation OFF Mode of Operation M_SET SET 180 VLV 67 ST 123 Target Temperature is 180F Normal operation system temperature is 123F For the motorized valve controlled by rela...

Page 15: ...adjustment valve position would perform at the close position Pump would be turn off after period of time set by the Pump Run On set point System Temperature Sensor fails Initial Synchronization Valv...

Page 16: ...and shows actual reading of the temperature sensor ST zz x 3 The lower line of the display shows possible adjustment for example NewSysTAdj 0 2 4 Press Up or Down key to make the reading equal to the...

Page 17: ...MCI Transformer 4 06 7345 1 5 10 9 7 6 Pump1 2 Pump1 1 Pump2 1 Pump2 2 9 5 12 4 8 13 14 Terminals Board J1 1 2 3 H H 8 9 10 11 12 13 14 7 4 5 6 1 2 J2 1 2 Transformer 1 9 5 4 8 9 5 Motor Controls comm...

Reviews: