intarblock | intartop
33
3. press
or
to modify its value.
4. press
set
to confirm then ew value and jump to the next parameter.
5. to exit the programming mode press set and
or wait for 15 seconds.
§
To lock the keyboard.-
1. press
and
for 3 s.
2. the message
“
POF
” will be shown and only the set point and temperature records can be
consulted.
3. To unblock the keyboard press
and
for 3 s.
27. PARAMETER LIST
Code
Description
Range
Default
List
MT
BT
REGULATION
SET
Set Point.
LS ÷ US
0 ºC
-20 ºC
Hy
Set Point differential.
0,1 ÷ 25,5 ºC
2,0 ºC
Pr1
LS
Minimum set point
-50,0 ºC ÷
SET
-5 ºC -25 ºC Pr2
US
Maximum set point.
SET ÷ 110,0 ºC 10 ºC -15 ºC Pr2
Od
S
Time in which functions excluding light are not allowed from
starting-up.
0 ÷ 255 min
1 min
Pr2
AC
Antishort cycle delay
0 ÷ 30 min
2 min
Pr1
CCt
Fast freezing mode time (minutes)
0 ÷ 23 h 50
min
0h
30 min
2h
30 min
Pr2
Con
Time interval during which the compressor is working after probe
default
0 ÷ 255 min
15 min
Pr2
CO
F
Time interval during which the compressor is stopped due to
probe default
0 ÷ 255 min
15 min
Pr2
DISPLAY
CF
Temperature measurement unit.
ºC - ºF
ºC
Pr2
rES
Resolution integer/decimal point (only if CF = ºC):
in (integer) = 1 ºC ; de (decimal) = 0,1 ºC.
in - de
de
Pr1
Lod
PARÁMETER NOT AVAILABLE FOR THIS MODEL
P1, P2, P3, 1r2
P1
Pr2
rEd
Remote display:
P1=room probe ; P2=evap. probe ; P3=ambient probe ; 1r2=P1-
P2.
P1, P2, P3, 1r2
P1
Pr2
DEFROSTING
tdF
Defrost type. (DO NOT MODIFY).
rE=electrical heater ; rT=off time ; in=hot gas injection
rE, rT, in
in
Pr1
EdF
Defrosting mode: in=Standar ; Sd=SmartDefrost
in - Sd
in
Pr2
SdF
set point for Smart Defrost.
-30,0 ÷ 30,0
ºC
0,0 ºC
Pr2
dtE
Defrosting finalization temperature.
-50,0
÷
110,0
ºC
20,0 ºC
Pr1