Applications Menu
Application Block Number 02
02.
RUN BELTWEIGHER
Select RUN BELTWEIGHER if not already in this application. Press side arrow after power
up when RUN (application) is displayed, key in password, enter and use side arrows to
select, then enter again.
For quicker commissioning first select Security Level 1 and connect the Hardlock link.
Going in to the Service menu select Calibrate, not view, in order to change settings. Change
Security levels and passwords last. Note that you make changes to the whole Service menu
block then press Enter.
It is advisable to first set up the Displays, Digital inputs, Function keys, then Beltweigher
Settings, then go to Precalibrate and set up loadcell values and scales. After this you can go
through the Service menu blocks to select and set other functions that you require.
Final calibration trim can be carried out on the system using Zero Trim (manual, length or
time) in Service menu or activate via Belt Zero using Function keys or Digital inputs. If test
weights are available use Span Trim. The Beltweigher has a Rate Correction Factor that can
be used later.
The Beltweigher Service menu contains the following function blocks. Details and operation
are listed in the Service menu section of this manual
01 Setpoint values
Set values for setpoints 1-6
02 Setpoint configuration
Select functions for setpoints 1-6
03 Analog output
Select output 1-5V, 0-10V, 0-20mA or 4-20mA
04 Communications
Select and set up serial output
05 Min/Max
Select minimum and/or maximum hold
06 Security level
Select access to Operator and/or Service menu
07 Precalibrate
Set loadcell values, excitation, range, damping
08 Zero trim
Trim empty belt (manual, length or time)
09 Span trim
Trim weighsection range using test weights
10 Beltweigher settings
Totalisers, weighsection, zerotrim, speed alarm
11 Correction factor
Set rate correction factor
12 Lineariser
Select up to 15 points of linearising
13 Simulate
For testing, force analog and relay outputs
14 Function keys
Set functions for keys F1-4
15 Digital inputs
Set functions for inputs D1-6
16 Displays
Set main display and up to 4 auxilliary on LCD
17 PI Control
Change beltweigher into mass flow controller
18 Transmitter settings
Set password, calibration, hardware & time/date