© 2022 instagrid All rights reserved
EN
9
3. SAFETY CONSIDERATIONS WHEN OPERATING THE INSTAGRID ONE MAX
3.1 Passive protection at the outlet / IT network
When connecting a load to the instagrid ONE max, a low-voltage network is established,
during the operation of which statutory regulations must be observed. It is the user's
responsibility to research and apply the locally applicable regulations – instagrid assumes no
liability in this regard.
The design of the instagrid ONE max ensures galvanic separation (isolation) between the
charging inlet
, the outlet
and housing, as well as between the
charging inlet and outlet. As a result, both the requirements placed on a protection class II
device are met and the feature of protective separation between inlet and outlet is
implemented. This means the outlet has no direct earth connection and is considered a special
safety feature, because in the event of an (individual) insulation fault, no shock current can
flow.
Such a network is referred to as an IT (isolé-terre) network. The operation of protection class I
loads on the instagrid ONE max is absolutely possible. The equipotential bonding of the two
outlets
is ensured through the design.
3.2 Active protection at the outlet
The outlet of the instagrid ONE max is protected from overload by several independently
overlapping mechanisms:
•
Energy content – due to the limited energy content of the integrated storage unit,
continuous current drain is not possible. The rated current of 16 A can be drained for a
maximum of 35 minutes; at 20 A for 27.5 minutes.
•
Thermally induced shutdown – the internal temperature of the instagrid ONE max is
monitored continuously during operation. Exceeding the fixed limit values leads to
a shutdown of the instagrid ONE max; see
. The time after which the
shutdown is triggered varies depending on ambient temperature and load current. At 25°C
and 16 A, a complete discharge of the instagrid ONE max (100% -> 0%) is possible without
triggering a shutdown.
•
Internal resistance – the internal resistance of the instagrid ONE max limits the possible
short-circuit current to values less than 500 A (peak).
•
Electronic fuse – during operation, the instagrid ONE max continuously measures the
outlet current actually flowing and calculates a temporal evaluation of the measured values.
Exceeding the fixed limit values leads to a shutdown of the instagrid ONE max; see
. The current/time characteristic resulting from the electronic fuse alone is within the
range that is typical for "B16"-type circuit breakers.
Furthermore, by means of a similarly redundantly active concept, special characteristics of the
output voltage are continuously monitored; e.g.:
•
Frequency
•
RMS voltage
•
Peak voltage
•
DC offset
3.3 Additional measures for increasing user safety
As shown in
and
, operation of a load on the instagrid ONE max
is accompanied by a high degree of electrical safety for the user. However, in special cases,
further increasing the scope of protective measures may be necessary. The following measures
are advised for this purpose:
•
Use of RCDs:
If more than one load is connected simultaneously to the instagrid ONE max (e.g. via a
power strip), then connecting an RCD (Residual Current Device) upstream for each load is
recommended.
Summary of Contents for ONE max
Page 1: ...USER MANUAL V2 0 ...
Page 18: ...instagrid co ...