15
Operations
4.5 Install the Access Panel
1.
Place the access panel on top of the server with the hood latch open. Allow the panel to
extend past the rear of the server.
2.
Push down on the hood latch. The access panel slides to a closed position.
3.
Use the screwdriver to tighten the security screw on the hood latch.
4.6 Install the Server
1.
After the installation/maintenance steps are completed, follow the installation guide and
lift the server chassis onto the rails. Push it into the rack.
2.
Use a screwdriver to fix the captive screws within the ears on both sides to secure the
chassis onto the rack.
WARNING:
A single server weighs above 60kg and should be lifted by at least four people or
by using auxiliary equipment.
4.7 Remove the GPU BOX
1.
Open the handles on both sides of the GPU BOX chassis, as shown by ① in the following figure.
Note:
Before opening the handles, check whether the screws on both sides of the chassis
are removed, if not removed, please remove them first to avoid damage to the handles.
2.
Pull the GPU BOX outward. When the buttons on both sides are exposed, press the two
buttons at the same time to pull the GPU BOX out of the chassis completely. The GPU BOX is