38
Parameter
Description
Silver coupon: 200 Å/month (compliant with the
gaseous corrosivity level of G1 defined in
ANSI/ISA-71.04-2013)
Particulate
Contaminants
Comply with the data centre cleaning standard
ISO 14644-1 Class 8
The server room must be free of explosive,
conductive, magnetic, and corrosive dust
It is recommended to hire a professional organization to monitor
the particulate contaminants in the server room.
Noise
(4, 5, 6, 7)
Noise emissions are measured in accordance with ISO
7779 (ECMA 74) and declared in accordance with ISO
9296 (ECMA 109). Listed are the declared A-weighted
sound power levels (LWAd) and the declared average
bystander position A-weighted sound pressure levels
(LpAm) at a server operating temperature of 23°C
(73.4°F):
Idle:
‐
LWAd: 5.9 Bels
‐
LpAm: 54.9 dBA
Operating:
‐
LWAd: 7.3 Bels
‐
LpAm: 67.2 dBA
1.
Not all configurations support the operating temperature range of 5°C to
35°C (41°F to 95°F). The GPU configuration supports the operating
temperature range of 10°C to 35°C (50°F to 95°F).
2.
Standard operating temperature:
-
10°C to 35°C (50°F to 95°F) is the standard operating temperature at
sea level. For temperatures between 10°C and 35°C (50°F and 95°F),
de-rate the maximum allowable temperature by 1°C per 305 m (1°F
per 556 ft) above sea level. The maximum temperature gradient is
20°C/h (36°F/h) and the maximum operating altitude is 3,050 m