background image

5

Electrical Connections

ELECTRIC SHOCK

 

 • Turn off the electrical supply to the disposer before  
  attempting any work on it. Use a voltmeter or  
  circuit tester to ensure that power is off.
 • All installation work must conform to local  

plumbing and electrical codes.

 • All control centers and disposers must be carefully 

and permanently grounded.

 • A properly fused disconnect must be installed at 

the electrical supply source for the control center. 

PROPERTY DAMAGE

 •  Ensure that control center voltage and phase 

match the disposer motor and electrical supply. 

Check name plates on disposer and control  

centers for voltage and phase specifications.

 • Refer to the control center wiring diagrams in this 

manual for correct connection.

 • Use NEMA 4 watertight electrical connectors  

(not supplied) when making electrical connections 

to the control center.

ELECTRICAL CONNECTIONS

Connect the incoming line power and disposer motor 
to the labeled terminal block in the control center. Use 
appropriate voltage and phase electrical connection 
diagrams at the back of this manual. Wire the disposer 
motor for the correct voltage using the connection  
diagram inside the motor terminal box.

Make sure the solenoid valve is the same voltage as the 
control panel and supply power.

Connect water solenoid valve as shown in the wiring 
diagrams on pages 7, 8, 9, and 10.

Wire per local electrical code using 7/8" diameter holes 
in bottom of control center cabinet and install NEMA 4 
watertight electrical connectors (not supplied).

After completing the connections, secure cover.  
Replace disposer motor cover.

TIME DELAY RELAY 

(Optional, not supplied with MS)

The time delay relay may be used with the MS to  
delay solenoid valve shut-off, providing a post flush. 
This helps prevents drain line stoppages and is  
beneficial when ground food waste must travel through 
many bends or a long horizontal run. It is adjustable 
from 0 to 10 minutes and factory set to provide  
approximately a 5 minute delay. To adjust, 

SHUT OFF 

ELECTRIC POWER

. Inside unit, locate the adjustment  

potentiometer. Turn clockwise to increase delay. Turn 
counterclockwise to decrease delay. See Figures 4 and 
5 for wiring.

Ensure the voltage rating on the time delay relay and 
solenoid valve are the same as the disposer motor  
and line voltage. 

1

3

6

4

Time Adjustment Knob

Figure 3. 120V or 208/230V Time Delay Relay

Figure 4. Time Delay Relay Connections - 120V or 208/230 V

Figure 5. Time Delay Relay Connection - 460V, 3-phase only

Summary of Contents for MS MS

Page 1: ...ons contained in this manual The Danger signal indicates an immediately hazardous situation which if not avoided will result in death or serious injury The Warning signal alerts you to potential hazar...

Page 2: ...anty FOODSERVICE DISPOSER CONTROL CENTER LIMITED WARRANTY InSinkErator Foodservice Disposer Control Centers are warranted against defects in material and workmanship for one year from the date of inst...

Page 3: ...4356 120V 1 1 2 2 MS 5 14356A 208 230V 1 1 2 2 MS 5 14356A 208 230V 3 1 2 5 MS 6 14356B 380 460V 3 1 2 10 FEATURES ENCLOSURE NEMA 4 construction PUSH BUTTON OPERATION Push Green button to start dispos...

Page 4: ...upplied is the proper voltage Make certain that the valves are plumbed according to water flow direction arrows marked on valves or the valves will not function properly The flow control valve regulat...

Page 5: ...diagram inside the motor terminal box Make sure the solenoid valve is the same voltage as the control panel and supply power Connect water solenoid valve as shown in the wiring diagrams on pages 7 8 9...

Page 6: ...e stop button and follow directions for unjamming that were supplied with the disposer D Water flows constantly before start button is pushed 1 Water solenoid valve is installed backward Water flow sh...

Page 7: ...enters and disposers must be carefully and permanently grounded A properly fused disconnect must be installed at the electrical supply source for the control center PROPERTY DAMAGE Ensure that the con...

Page 8: ...l centers and disposers must be carefully and permanently grounded A properly fused disconnect must be installed at the electrical supply source for the control center PROPERTY DAMAGE Ensure that the...

Page 9: ...s and disposers must be carefully and permanently grounded A properly fused disconnect must be installed at the electrical supply source for the control center PROPERTY DAMAGE Ensure that the control...

Page 10: ...rs and disposers must be carefully and permanently grounded A properly fused disconnect must be installed at the electrical supply source for the control center PROPERTY DAMAGE Ensure that the control...

Reviews: