Controller is equipped with a fresh water cir-

culating pump control function (

P2 pump

). 

Control of fresh water circulating pump can 

be done in two ways:

1. 

Control based on return 

temperature of fresh water 

circulation. If fresh water 

pump control is by this me-

thod, special symbol is visible on di-

splay. 

T4

 sensor must be connected to 

use this control method. Fresh water 

circulation pump is turned on when 

temperature on 

T4

 sensor drops be-

low set value. It is recommended that 

T4

 sensor be placed on return pipe of 

fresh water circulation or just before 

last fresh water receiver. To this place, 

fresh hot water will be pushed  and 

then fresh water pump will be turned 

off. Just as water pipe in the circula-

ting pump will cool down, fresh water 

circulation pump will be turned on. 
Attention. If the temperature in the 

upper part of tank No 1 (T3) is too 

low to warm T4 sensor to desired 

temperature, the circulation pump 

will not be turned on.

2. 

Control based on time pe-

riods. f fresh water pump 

control is by this method, 

special symbol is visible on 

display. Controller controls fresh water 

pump according to periods of time: 

work time

 and 

break time

. E.g. Cir-

culation pump is turned on every 20 

min for 3 min. Both periods are 

adjustable.

 

e

If on display is not showed any of above 

symbols, this means that fresh water cir-

culation pump is not controlled by con-

troller at all.

 

e

If fresh water circulation pump is wor-

king 

P2

 symbol on display is flashing. 

 

e

Fresh water circulation pump is control-

led only in set daily periods of time (only 

between beginning and end of the pe-

riod). Often there is no need for circula-

tion pump control during the night or 

when no one is in the building. Apart 

from these periods circulation pump 

never turns on.

To choose method of control of fresh water 

circulation pump please:

Repeatedly press the button.

Press and hold button.

Repeatedly press the button to set 

further parameters:

T4on

 - Value of temperature [ºC] 

below which fresh water circula-

tion pump is turned on (parameter 

adjustment available only for first 

method of control)

T4off

 - Hysteresis between turning 

on and turning off fresh water cir-

culation pump (parameter adju-

stment only for first method of 

control)

on

 - Work time period [min] - how 

long the pump has to work in one 

cycle (parameter adjustment ava-

ilable only for second method of 

control)

After selecting control method, you can set 

the parameters of control function. Depen-

ding on selected control method there are 

different parameters settings. To adjust para-

meters of function please:

f

OuRTh

 

sysTEm

 - T

WO

 

cOllEcTORs

 

aREas

 

and

 

TWO

 

Tanks

Circulation pump of the first collectors area 

(P1) is started when temperature difference 

of the first collectors area (T1) and tempera-

ture in the target tank (T2 or T5) reaches the 

set value of switching on. Similarly, circula-

tion pump of the second collectors area (P0) 

is started when temperature difference of 

the second collectors area (T0) and tempera-

ture in the target tank (T2 or T5) reaches the 

set value of switching on. Circulation pumps 

(P1 and P0) are working independently from 

each other - the pumps may work simultane-

ously, don’t work at all or one pump works. 

Three-way valve (R2) is set in the position to 

load appropriate tank. Tanks are loaded ac-

cording to the selected priority (description 

is later in this manual). Suitable loading pump 

is turned off when temperature difference 

between the suitable collectors area and 

the loaded tank falls below the set value of 

switching off or  temperature in the tank (T2 

or T5) reaches the set maximum value. The 

Pump of collectors is controlled with conti-

nuously speed adjustment.

There is a posibility to pump heat between 

tanks (description is later in this manual).

This system is recommended when areas of 

the collectors are working independently for 

each other (east-west layout with a low slope, 

there may be a case when two collectors are-

as are working simultaneously).

External power supply (H2) works as in the 

third system.

In fact, the second collectors area may be re-

spectively hydraulically connected another 

device which produces thermal energy for 

example: heating fireplace.

In fact, the second tank may be respectively 

hydraulically connected swimming pool.

       Day 

T1

T3

T6

T5

T2

H1

T4

T0

1

P2

P

P1

P0

System

2

H2

Summary of Contents for IB-TRON 4000 SOL

Page 1: ...Multisystem solar controller With support for additional devices two collectors areas for central and water heating IB Tron 4000 SOL ...

Page 2: ... Fresh water circulation pump_________ 10 Bacteriological protection____________ 11 Hysteresis_________________________ 11 Extra heating busters________________ 11 Frost protection____________________ 13 High temperature protection_________ 13 Choice of tank______________________ 14 Loading pumps____________________ 14 P0 and P1 pump speed______________ 15 SMART START______________________ 17 GUAR...

Page 3: ...ction in two modes de pends of user setting Winter heating building only Fresh water tank is not heated at all by so lar and other heating busters Summer cooling tanks and extra heating busters not working at all e e Bacteriological protection of fresh wa ter tank e e GUARD function protection devices from damage e e Reloading heat between tanks e e SMART START function controller in telligently c...

Page 4: ...T1 T3 T6 T5 T2 H1 T4 T0 1 P System 2 H2 P0 P2 P3 R1 P1 e e The appearance of display depending of chosen system of work Some items may not be visible e e Flashing pump symbol means that this pump works at the moment If the sym bol is not flashing means that pump does not work now I IWith controller are provided follow sensors 2x PT1000 Sensors connected to T0 and T1 5x NTC10kOhm Sensors connected ...

Page 5: ...0 1 057 20 1 097 30 1 136 40 1 175 50 1 215 60 1 254 70 1 292 80 1 331 90 1 370 100 1 408 110 1 447 120 1 485 130 1 523 140 1 561 150 1 599 160 1 597 170 1 645 180 1 712 190 1 750 200 1 787 210 1 774 220 1 810 230 1 847 240 1 875 250 1 912 260 2 008 270 2 045 280 2 081 Calibration After properly connecting controller is ready to work Controller is factory calibrated to work with standard sensors H...

Page 6: ...king simultaneously In fact the second collectors area may be re spectively hydraulically connected another device which produces thermal energy for example heating fireplace when temperature difference of the second collectors area T0 and temperature in the tank T2 reaches the set value of switching on Circulation pumps P1 and P0 are wor king independently from each other the pumps may work simul...

Page 7: ...r circula tion pump is turned on parameter adjustment available only for first method of control T4off Hysteresis between turning on and turning off fresh water cir culation pump parameter adju stment only for first method of control on Work time period min how long the pump has to work in one cycle parameter adjustment ava ilable only for second method of control After selecting control method yo...

Page 8: ...nal linear weather compensator Such controllers are available in our offer Fresh water circulation pump Bacteriological protection Bacteriological protection Extra heating busters off Break time period min ever this time period circulation pump will be turned on parameter ad justment available only for second method of control P1 on Beginning of first period of work P1 off End of first period of w...

Page 9: ...lease do not confuse energy with temperature To adjust parameters of this function please Press and hold button Repeatedly press the button to set further parameters 1 OptimalT2temperature for first method of choice 2 Method of tank choice by former description Set desired value of the parameter Confirm set data OK AH AH High temperature protection High temperature protection Frost protection Cont...

Page 10: ...t data OK Loading pumps Loading pumps Solar system for whole day heat both tanks completely 1 and 2 First tank is fresh water tank At evening residents of building cool first tank hey used hot water Normally at this point extra heating buster should be turned on to heat fresh water tank such as electric heater extra heating buster feature has been previously described in this manu al However when ...

Page 11: ...erefore in fact often happens that collec tor could start work earlier few minutes than this happened in practice While in days with high solar radiation this energy losses arising from this delay is negligible but in winter days with lower solar radiation there is quite a lot of this energy losses To solve this problem and increase energy output IB Tron 4000SOL controller is equip ped with a spec...

Page 12: ... function setting Tmax Temperature units Press and hold two buttons simultaneously Tmin Tmax Software version Press and hold two buttons simultaneously Tmax OK T Test functions In addition there is possible to test logic of system work by sensor test function When this function is on sensors no longer making real measurement user are able to simulate absolute values from controller keyboard contro...

Page 13: ...e Warranty fore its purchase sale at distance it is possible to return goods within 10 days Returned goods cannot bear signs of exploitation itmustcontainallelements with which it was delivered e e In the case of return of purchased go ods all shipping costs are on buyer side Before return of goods please contact with seller e e Terms of warranty may be changed by local InsBud company partner Shor...

Page 14: ...ul Niepodlegości 16a 32 300 Olkusz POLAND tel fax 48 32 643 26 87 e mail insbud insbud net ...

Reviews: