Chapter 4 Functional Parameters
-
36
-
If OP is shorted to DC+, input terminals X15 to X20 are low level active. If OP is shorted
to DC-, X15 to X20 are high level active. The other input terminals are low level active and
become ON when they are shorted to 0V.
The function of a terminal indicated by an LED segment in the preceding figure may be
valid when this segment is ON or OFF. Whether this function is valid at segment ON or
OFF is decided by the NO/NC feature of the terminal. Y1F to Y4F are detection signals and
indicate the action state of the detected relays Y1 to Y4. In normal state, Y1F to Y4F are
ON or FF with Y1 to Y4 simultaneously.
Parameter
Name
Setting Range
Factory Setting Unit Operation
F1-14
Number of pulses
per second at
nominal speed
-
0
-
●
It indicates the number of phase A/B pulses per second at nominal speed, which is
calculated based on parameters in group F0.
Parameter
Name
Setting Range
Factory Setting Unit Operation
F1-15
Number of pulses
for 1.2 times of
braking-to-stop
distance
-
0
-
●
It indicates the number of phase A/B pulses for 1.2 times of braking-to-stop distance, which
is calculated based on parameters in group F0.
Parameter
Name
Setting Range
Factory Setting Unit Operation
F1-16
Number of pulses
between two
adjacent step
signals
-
0
-
●
It indicates the number of phase A/B pulses between two adjacent step signals, which is
calculated based on parameters in group F0 and the escalator step of 40 cm wide.
Parameter
Name
Setting Range
Factory Setting Unit Operation
F1-17
ER-00
-
0
-
●
It indicates the faults that have occurred and need to be reset manually. Each fault is
allocated with a bit. The corresponding relationship is as follows:
Bit0: Err01; Bit1: Err02; ……Bit15: Err16
After the system reports the fault, the corresponding bit will become valid and is saved in
F1-17 after being converted to a decimal number.