5.1 Pushbutton Operation Instructions
1. Connect the required accessories to the inoRAC by following the accessory
instructions.
2. Connect 120 VAC to the inoRAC via the receptacle on the side of the control
enclosure.
3. Turn on the inoRAC by placing the ON/OFF switch on the side of the control
enclosure into the “ON” position.
4. Start the inoRAC by pressing the “Racking Unit Control” button on the Operator
Panel.
5. Ensure the inoRAC is not connected to a circuit breaker. Ensure the inoRAC
is free to operate all accessories. Follow the Operator Panel instructions for
calibrating the inoRAC.
6. Select the operation to be performed, “Operate Pushbutton” on the Operator
Panel.
7. Adjust the inoRAC height to the level of the pushbutton to press via the “Raise”
and “Lower” buttons on the Operator Panel.
8. Place the inoRAC 2” from the pushbutton you are needing to press.
9. Set the brakes on the inoRAC.
10. Move to a safe location outside the arc flash hazard boundary with the Operator
Panel.
11. Follow the Operator Panel instructions for pressing the pushbutton.
12. Turn off the inoRAC by placing the ON/OFF switch on the side of the control
enclosure into the “OFF” position.