5.1 Setpoint
To enter press OK, it will show the following screen:
The calculation of the production is made by setting of two setpoints, A and B, and
the % of production that is desired for each of those points.
-
When the ORP is below the lower set point, the signal will work at its maximum
frequency.
-
When the ORP is between both points, the chlorinator will send a proportional
signal defined by both points. For example, in the case of the figure, if the ORP is at
675 mV the pump will dose at 50%.
-
When the ORP is above the upper set point, the equipment will keep the output
OFF, at 0%.
You can set both points and choose the percentage of dosage for each of them. To
make this, press cursor with the
MENU
key in the parameter you want to modify
and scroll with the arrows to change the value.
Press
OK
key to save the data and Exit the sub
-
menu.
By setting the set points you will be defining at the same time the % of production
desired in each of those points, both dependent on the size of your pool. For
example, if your pool has a high volume you should establish high production
percentages. The response time in the measurement of the ORP of your pool can be
considered when establishing the set point B by cutting the signal before reaching
ORP Config.
2 Setpoints
A: RH 650mV 80%
B: RH 700mV 20%
A: RH 650mV 80%
B: RH 700mV 20%