X
X
★
X
Open or short circuit of T2 temperature sensor
E1
——
X
★
X
X
Indoor / outdoor units communication error
E2
——
X
X
X
★
Full-water malfunction
E3
——
★
★
X
X
Indoor EEPROM malfunction
E4
——
★
X
X
IPM module protection
E5
P4
★
X
X
Open or short circuit of T3 or T4 temperature
sensor or outdoor EEPROM malfunction
E6
E0,E4
★
★
X
Outdoor fan has been out of control
E7
——
★
X
Voltage protection
P0
E5
★
★
★
★
Temperature protection of compressor top.
P3
P0
★
◎
X
X
Inverter compressor drive protection
P4
P7
★
X
X
Mode conflict
P5
——
★
flash at 2.5Hz,
light, X extinguished
◎
flash at 1Hz
Outdoor unit error code explanation:
Display
digital tube
LED STATUS
IDU
Error
(Vertu/Luna)
IDU
Error
(MTBI(MTBU))
E0
Outdoor EEPROM malfunction
E5
E6
E1
No A Indoor unit coil outlet temp. sensor or connector of sensor is defective
——
——
E2
No B Indoor unit coil outlet temp. sensor or connector of sensor is defective
——
——
E3
No C Indoor unit coil outlet temp. sensor or connector of sensor is defective
——
——
E6
No D Indoor unit coil outlet temp. sensor or connector of sensor is defective
——
——
E4
Open or short circuit of outdoor temperature sensor(T4)
E5
E6
E5
Voltage protection
P1
P0
E7
Communication malfunction between IPM board and outdoor main board
——
——
P0
Temperature protection of compressor discharge (Temperature protection of
compressor top(only for VOM20H2RE102&VOM30H2RE103) )
P2
P3(P1)
P1
High pressure protection (Only for VOM42H2RE104)
——
——
P2
Low pressure protection(Only forVOM42H2RE104)
——
——
P3
Current protection of compressor
——
——(P2)
P4
IPM module protection
P0
E5
P6
High temperature protection of condenser
——
——
P7
Inverter compressor drive protection
P4
P4
PF
PFC module protection(Only for VOM42H2RE104)
——
——