35
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following
Fan speed
T2-T1
Note
High
TH
DEFROST
If indoor fan is in high speed and T2-T1< TH
DEFROST
, start defrosting
Medium
TM
DEFROST
If indoor fan is in medium speed and T2-T1< TM
DEFROST
, start defrosting
Low
TL
DEFROST
If indoor fan is in low speed and T2-T1< TL
DEFROST
, start defrosting
Breeze or stop
/
If indoor fan is breezing or stopped, start defrosting
Calculate from the end of latest defrost, evaporator high temp. Protection only closes outdoor fan
with the compressor still running add up to 90 minutes.
2) Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to
normal heating mode.
(1) The defrosting time is reached to the setting value.
(2) The compressor current reaches or exceeds
DEFROST
for 7 seconds.
3) Defrosting action
During the defrosting mode, if the machine stopped or transferred to other mode, the defrosting mode
will stop, and all the defrosting conditions will be cleared.
Summary of Contents for Oasis WOE10C2DB1 / HOE10C2MR83
Page 14: ...12 5 Wiring Diagram 5 1 Indoor Units WOE10C2DB8 WOE13C2DB8 WOE18C2DB8 WOE24C2DB8 ...
Page 15: ...13 5 2 Outdoor Units HOE10C2MR83 HOE13C2MR83 HOE18C2MR83 ...
Page 16: ...14 HOE24C2MR83 ...
Page 48: ...46 9 2 2 Open circuit or short circuit of temperature sensor diagnosis and solution ...
Page 49: ...47 9 2 3 Over current protection occurs 4 times diagnosis and solution ...
Page 51: ...49 9 2 6 Indoor outdoor units communication error diagnosis and solution ...