25
needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the
air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at
a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way
valve’s service port immediately.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
Electronic scale
Summary of Contents for Oasis WOE10C2DB1 / HOE10C2MR83
Page 14: ...12 5 Wiring Diagram 5 1 Indoor Units WOE10C2DB8 WOE13C2DB8 WOE18C2DB8 WOE24C2DB8 ...
Page 15: ...13 5 2 Outdoor Units HOE10C2MR83 HOE13C2MR83 HOE18C2MR83 ...
Page 16: ...14 HOE24C2MR83 ...
Page 48: ...46 9 2 2 Open circuit or short circuit of temperature sensor diagnosis and solution ...
Page 49: ...47 9 2 3 Over current protection occurs 4 times diagnosis and solution ...
Page 51: ...49 9 2 6 Indoor outdoor units communication error diagnosis and solution ...