8.3 Main Protection
8.3.1 Time Delay at restart for compressor.
8.3.2 Fan Speed is out of control. (Only for 7k,9k, 12k,16k, 17k,
----When Indoor Fan Speed keeps too low or too high for certain time, the unit will stop and the LED
will display the failure
8.3.3 Current protection
I3SEC
I5MIN
A
B
C
Resume
IFAN
IRESTORE
A zone: The current exceeds
I
3SEC
for 5 second, the compressor and outdoor fan will shut off. (For 9k,
12k, 17k,18k models)
A zone: The current exceeds
I
3SEC
for 3 second, the compressor and outdoor fan will shut off. (For21k,
24k models)
B zone: The current exceeds
I
5min
for 5 minute, the compressor and outdoor fan will shut off.
C zone: The current exceeds
I
FAN
,
the outdoor fan will shut off if AC is in heating mode. If AC is in
cooling mode, the indoor fan will run at low speed.
While
8.3.4 Zero crossing detection error protection (Only for 9k, 12k, 16k,17k,
If AC can not detect zero crossing signal for 4 minutes or the zero crossing signal time interval is not
correct, the unit will stop and the LED will display the failure. The correct zero crossing signal time
interval should be between 6-13ms.
8.3.5 Indoor / outdoor units communication protection (only for 21k,24k models)
If the indoor units can not receive the feedback signal from the outdoor units for 2 minutes, the AC will
stop and display the failure.
Summary of Contents for Oasis WOE10C2DB1 / HOE10C2MR83
Page 14: ...12 5 Wiring Diagram 5 1 Indoor Units WOE10C2DB8 WOE13C2DB8 WOE18C2DB8 WOE24C2DB8 ...
Page 15: ...13 5 2 Outdoor Units HOE10C2MR83 HOE13C2MR83 HOE18C2MR83 ...
Page 16: ...14 HOE24C2MR83 ...
Page 48: ...46 9 2 2 Open circuit or short circuit of temperature sensor diagnosis and solution ...
Page 49: ...47 9 2 3 Over current protection occurs 4 times diagnosis and solution ...
Page 51: ...49 9 2 6 Indoor outdoor units communication error diagnosis and solution ...