2.4.2.12. P6 malfunction
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or
close to 0, the IPM is defective. Otherwise, please follow the procedure below:
P6 display
P6 display
IPM module protection
IPM module protection
Yes
Check whether the power voltage
is normal.
Check whether the power voltage
is normal.
Measure whether outdoor terminal
voltage is normal
?
Measure whether outdoor terminal
voltage is normal
?
Restart the unit when the power supply
gets normal
Restart the unit when the power supply
gets normal
No
Yes
No
Reconnect it well
Reconnect it well
Yes
Measure whether the voltage
between L and N is normal
?
Measure whether the voltage
between L and N is normal
?
Yes
Measure whether input voltage of
bridge rectifier is normal
?
Measure whether input voltage of
bridge rectifier is normal
?
No
No
Check the wiring of
power wires well or
correctly
Check the wiring of
power wires well or
correctly
Reconnect it well
Reconnect it well
Check the wiring of L
and N well or correctly
Check the wiring of L
and N well or correctly
Reconnect it well
Reconnect it well
Check the wiring of
bridge rectifier well or
correctly
Check the wiring of
bridge rectifier well or
correctly
No
No
Yes
Replace the PFC module(If has)
Replace the PFC module(If has)
No
Measure whether the voltage
between P and N is normal
refer to the
Appendix
3
?
Measure whether the voltage
between P and N is normal
refer to the
Appendix
3
?
Replace the bridge rectifier
Replace the bridge rectifier
No
Check whether bridge
rectifier is normal
Check whether bridge
rectifier is normal
Check the wiring of reactor
or inductance
Check the wiring of reactor
or inductance
Reconnect the wiring
Reconnect the wiring
No
Check whether reactor or
inductance is normal
Check whether reactor or
inductance is normal
Yes
Replace reactor or
inductance
Replace reactor or
inductance
No
Check whether the connecting
wire between main board and the
IPM board is connected tightly
Check whether the connecting
wire between main board and the
IPM board is connected tightly
Reconnect it well
Reconnect it well
No
Check if the outdoor unit
ventilation is good
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Make the outdoor unit ventilate well
Check whether the refrigerant system is ok
Check whether the refrigerant system is ok
No
Check if the outdoor fan runs
properly
Check if the outdoor fan runs
properly
please refer to the solution of fan speed
has been out of control malfunction .
Find out the cause and have it solved.
please refer to the solution of fan speed
has been out of control malfunction .
Find out the cause and have it solved.
No
Yes
No
Yes
Yes
Check the compress is
normal
Check the compress is
normal
Yes
Replace the compressor
Replace the compressor
No
Replace IPM board
Replace IPM board
Replace the outdoor main PCB
Replace the outdoor main PCB
No
Check whether the connecting
wire of the compressor is
connected correctly or tightly
Check whether the connecting
wire of the compressor is
connected correctly or tightly
Reconnect it well
Reconnect it well
No
Yes
Yes
86
Electrical Control System
Summary of Contents for ICS0629C21
Page 1: ...SERVICE MANUAL IOS629C2V01 IOS736C2V01 IUS0736C21 ICS0629C21 ICS0736C21 AIR CONDITIONER i ...
Page 2: ......
Page 4: ......
Page 9: ...Part 2 Indoor Units Four way Cassette Type 6 Ceiling Floor Type 20 5 ...
Page 13: ......
Page 16: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12 Four way Cassette Type ...
Page 17: ...Wiring Diagrams 4 Wiring Diagrams ICS0629C21 ICS0736C21 Four way Cassette Type 13 ...
Page 23: ...Field Wiring 11 Field Wiring ICS0629C21 ICS0736C21 Four way Cassette Type 19 ...
Page 27: ...Service Space 3 Service Space Ceiling Floor Type 23 ...
Page 28: ...Wiring Diagrams 4 Wiring Diagrams IUS0736C21 24 Ceiling Floor Type ...
Page 35: ...Field Wiring 11 Field Wiring IUS0736C21 Ceiling Floor Type 31 ...
Page 40: ...Wiring Diagrams 3 Wiring Diagrams IOS629C2V01 36 Outdoor Unit ...
Page 41: ...Wiring Diagrams IOS736C2V01 Outdoor Units 37 ...