Troubleshooting
2.4.2.9. P3 malfunction
P3 display
P3 display
Current protection of compressor
Current protection of compressor
The protection occurred in
standby
The protection occurred in
standby
Yes
Yes
Measure whether the
current is normal
?
Measure whether the
current is normal
?
Yes
No
Replace the outdoor main PCB
Replace the outdoor main PCB
Check whether the power
voltage is normal.
Check whether the power
voltage is normal.
Measure whether outdoor
terminal voltage is normal
?
Measure whether outdoor
terminal voltage is normal
?
Restart the unit when the power
supply gets normal
Restart the unit when the power
supply gets normal
No
Yes
No
Reconnect it well
Reconnect it well
Yes
Measure whether the voltage
between L and N is normal
?
Measure whether the voltage
between L and N is normal
?
Yes
Measure whether input voltage
of bridge rectifier is normal
?
Measure whether input voltage
of bridge rectifier is normal
?
No
No
Check the wiring of
power wires well or
correctly
Check the wiring of
power wires well or
correctly
Reconnect it well
Reconnect it well
Check the wiring of
L and N well or
correctly
Check the wiring of
L and N well or
correctly
Reconnect it well
Reconnect it well
Check the wiring of
bridge rectifier well
or correctly
Check the wiring of
bridge rectifier well
or correctly
No
No
Yes
Replace the PFC module(If has)
Replace the PFC module(If has)
No
Measure whether the voltage
between P and N is normal
refer to the
Appendix
3
?
Measure whether the voltage
between P and N is normal
refer to the
Appendix
3
?
Replace the bridge
rectifier
Replace the bridge
rectifier
No
Check whether
bridge rectifier is
normal
Check whether
bridge rectifier is
normal
Check the wiring of
reactor or inductance
Check the wiring of
reactor or inductance
Reconnect the
wiring
Reconnect the
wiring
No
Check whether reactor
or inductance is normal
Check whether reactor
or inductance is normal
Yes
Replace reactor or
inductance
Replace reactor or
inductance
No
Check whether the outdoor
ambient temperature is
higher than 50
℃
Check whether the outdoor
ambient temperature is
higher than 50
℃
No
Stop the unit
Stop the unit
Yes
Check if the outdoor unit
ventilation is good
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Make the outdoor unit ventilate well
Check whether the heat
exchanger is dirty
Check whether the heat
exchanger is dirty
No
Clean the heat exchanger
Clean the heat exchanger
Yes
Check whether the refrigerant
system is ok
Check whether the refrigerant
system is ok
Replace outdoor main
board
Replace outdoor main
board
No
No
Check if the outdoor fan
runs properly
Check if the outdoor fan
runs properly
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
No
Yes
No
Yes
Yes
Check whether system pressure
is too high
Check whether system pressure
is too high
Recycle the over charged
refrigerant
Recycle the over charged
refrigerant
Yes
Electrical Control System
83
Summary of Contents for ICS0629C21
Page 1: ...SERVICE MANUAL IOS629C2V01 IOS736C2V01 IUS0736C21 ICS0629C21 ICS0736C21 AIR CONDITIONER i ...
Page 2: ......
Page 4: ......
Page 9: ...Part 2 Indoor Units Four way Cassette Type 6 Ceiling Floor Type 20 5 ...
Page 13: ......
Page 16: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12 Four way Cassette Type ...
Page 17: ...Wiring Diagrams 4 Wiring Diagrams ICS0629C21 ICS0736C21 Four way Cassette Type 13 ...
Page 23: ...Field Wiring 11 Field Wiring ICS0629C21 ICS0736C21 Four way Cassette Type 19 ...
Page 27: ...Service Space 3 Service Space Ceiling Floor Type 23 ...
Page 28: ...Wiring Diagrams 4 Wiring Diagrams IUS0736C21 24 Ceiling Floor Type ...
Page 35: ...Field Wiring 11 Field Wiring IUS0736C21 Ceiling Floor Type 31 ...
Page 40: ...Wiring Diagrams 3 Wiring Diagrams IOS629C2V01 36 Outdoor Unit ...
Page 41: ...Wiring Diagrams IOS736C2V01 Outdoor Units 37 ...