Capacity Tables
5. Capacity Tables
5.1 Cooling Capacity
ICS0629C21
Cooling
Outdoor conditions (DB)
Indoor Conditions
(kW)
21ºC
28ºC
35ºC
43ºC
21/15ºC DB/WB
TC
7.52
7.15
6.79
6.50
SC
5.56
5.51
5.43
5.46
Input
2.10
2.28
2.38
2.46
24/17ºC DB/WB
TC
7.74
7.37
7.01
6.57
SC
5.80
5.75
5.68
5.52
Input
2.23
2.38
2.49
2.61
27/19ºC DB/WB
TC
7.88
7.52
7.30
6.79
SC
5.83
5.79
5.69
5.57
Input
2.28
2.41
2.54
2.66
32/23ºC DB/WB
TC
8.03
7.74
7.59
7.01
SC
6.83
6.73
6.68
6.52
Input
2.38
2.49
2.66
2.76
ICS0736C21
Cooling
Outdoor conditions (DB)
Indoor Conditions
(kW)
21ºC
28ºC
35ºC
43ºC
21/15ºC DB/WB
TC
11.33
10.78
10.23
9.79
SC
8.38
8.30
8.18
8.22
Input
3.42
3.71
3.88
4.00
24/17ºC DB/WB
TC
11.66
11.11
10.56
9.90
SC
8.75
8.67
8.55
8.32
Input
3.63
3.88
4.04
4.25
27/19ºC DB/WB
TC
11.88
11.33
11.00
10.23
SC
8.79
8.72
8.58
8.39
Input
3.71
3.92
4.13
4.33
32/23ºC DB/WB
TC
12.10
11.66
11.44
10.56
SC
10.29
10.14
10.07
9.82
Input
3.88
4.04
4.33
4.50
Notes:
TC : Total capacity ; kW
SC: Sensible heat capacity ; kW
Input: Input
power; kW
14
Four-way Cassette Type
Summary of Contents for ICS0629C21
Page 1: ...SERVICE MANUAL IOS629C2V01 IOS736C2V01 IUS0736C21 ICS0629C21 ICS0736C21 AIR CONDITIONER i ...
Page 2: ......
Page 4: ......
Page 9: ...Part 2 Indoor Units Four way Cassette Type 6 Ceiling Floor Type 20 5 ...
Page 13: ......
Page 16: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12 Four way Cassette Type ...
Page 17: ...Wiring Diagrams 4 Wiring Diagrams ICS0629C21 ICS0736C21 Four way Cassette Type 13 ...
Page 23: ...Field Wiring 11 Field Wiring ICS0629C21 ICS0736C21 Four way Cassette Type 19 ...
Page 27: ...Service Space 3 Service Space Ceiling Floor Type 23 ...
Page 28: ...Wiring Diagrams 4 Wiring Diagrams IUS0736C21 24 Ceiling Floor Type ...
Page 35: ...Field Wiring 11 Field Wiring IUS0736C21 Ceiling Floor Type 31 ...
Page 40: ...Wiring Diagrams 3 Wiring Diagrams IOS629C2V01 36 Outdoor Unit ...
Page 41: ...Wiring Diagrams IOS736C2V01 Outdoor Units 37 ...