47
Temperature Sensors.
Room temp.(T1) sensor,
Indoor coil temp.(T2) sensor,
Outdoor coil temp.(T3) sensor,
Outdoor ambient temp.(T4) sensor,
Compressor discharge temp.(T5) sensor.
Measure the resistance value of each winding by using the multi-meter.
Table 1: Some frequently-used R-T data for T1,T2,T3 and T4 sensor:
Temperature (
)
5
10
15
20
25
30
40
50
60
Resistance Value (K
5
)
26.9 20.7 16.1 12.6 10
8
5.2 3.5 2.4
Table 2: Some frequently-used R-T data for T5 sensor:
Temperature (
)
5
15
25
35
60
70
80
90
100
Resistance Value (K
5
)
141.6 88
56.1 36.6 13.8 9.7 6.9 5
3.7
Resistance value (K
5
)
Temperature (
)
T5
T1,T2,T3,T4
Summary of Contents for BIN312C2V31
Page 1: ...CSI 1206 A SERVICE MANUAL BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 AIR CONDITIONER ...
Page 12: ...10 Model R mm L mm H mm Dimension of installation hole mm BIN625C2V31 106 5 70 45 65 ...
Page 16: ...14 5 Wiring Diagram 5 1 Indoor Unit BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 ...
Page 17: ...15 5 2 Outdoor Unit BIN312C2V31 BIN520C2V31 ...
Page 18: ...16 BIN625C2V31 BIN414C2V31 202037391056 ...
Page 40: ...38 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution ...
Page 41: ...39 9 2 2 Indoor outdoor units communication protection diagnosis and solution ...
Page 42: ...40 9 2 3 Zero crossing signal diagnosis and solution ...
Page 43: ...41 9 2 4 Indoor fan speed has been out of control diagnosis and solution ...
Page 44: ...42 9 2 5 Open or short circuit of temperature sensor diagnosis and solution ...
Page 45: ...43 9 2 6 IPM malfunction or IGBT over strong current protection diagnosis and solution ...
Page 46: ...44 9 2 7 Over voltage or too low voltage protection diagnosis and solution ...