6.3 Pipe length and the elevation
Pipe size
Capacity
Btu/h
Gas
Liquid
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
9k
3/8’’
( 9.52)
1/4’’
( 6.35)
5
8
20
20
12k,15k
1/2’’
( 12.7)
1/4’’
( 6.35)
5
8
20
20
18k
1/2’’
( 12.7)
1/4’’
( 6.35)
5
10
25
20
24k
5/8’’
( 16)
3/8’’
( 9.52)
5
10
25
40
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
The oil trap should be installed per 5-7 meters.
Summary of Contents for BIN312C2V31
Page 1: ...CSI 1206 A SERVICE MANUAL BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 AIR CONDITIONER ...
Page 12: ...10 Model R mm L mm H mm Dimension of installation hole mm BIN625C2V31 106 5 70 45 65 ...
Page 16: ...14 5 Wiring Diagram 5 1 Indoor Unit BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 ...
Page 17: ...15 5 2 Outdoor Unit BIN312C2V31 BIN520C2V31 ...
Page 18: ...16 BIN625C2V31 BIN414C2V31 202037391056 ...
Page 40: ...38 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution ...
Page 41: ...39 9 2 2 Indoor outdoor units communication protection diagnosis and solution ...
Page 42: ...40 9 2 3 Zero crossing signal diagnosis and solution ...
Page 43: ...41 9 2 4 Indoor fan speed has been out of control diagnosis and solution ...
Page 44: ...42 9 2 5 Open or short circuit of temperature sensor diagnosis and solution ...
Page 45: ...43 9 2 6 IPM malfunction or IGBT over strong current protection diagnosis and solution ...
Page 46: ...44 9 2 7 Over voltage or too low voltage protection diagnosis and solution ...