33
F: Keep the current frequency.
G: Decrease the frequency to the lower level until to F1.
H: Run at F1 for 1h.(if T1-Ts<-2 , compressor will stop)
Meanwhile, the compressor running frequency is limited by the current.
Off: Compressor stop.
Decrease: Decrease the running frequency to the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
Note:
When AC is in “hold” zone for 3 minutes, the compressor frequency will rise to the higher level.
(frequency will increase twice at most)
8.4.2.2 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and
auto.
Auto fan in cooling mode acts as follow:
Current
(A)
I3COOL
I2COOL
I1COOL
Compressor off
Frequency decrease
Frequency hold
Normal operation
Summary of Contents for BIN312C2V31
Page 1: ...CSI 1206 A SERVICE MANUAL BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 AIR CONDITIONER ...
Page 12: ...10 Model R mm L mm H mm Dimension of installation hole mm BIN625C2V31 106 5 70 45 65 ...
Page 16: ...14 5 Wiring Diagram 5 1 Indoor Unit BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 ...
Page 17: ...15 5 2 Outdoor Unit BIN312C2V31 BIN520C2V31 ...
Page 18: ...16 BIN625C2V31 BIN414C2V31 202037391056 ...
Page 40: ...38 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution ...
Page 41: ...39 9 2 2 Indoor outdoor units communication protection diagnosis and solution ...
Page 42: ...40 9 2 3 Zero crossing signal diagnosis and solution ...
Page 43: ...41 9 2 4 Indoor fan speed has been out of control diagnosis and solution ...
Page 44: ...42 9 2 5 Open or short circuit of temperature sensor diagnosis and solution ...
Page 45: ...43 9 2 6 IPM malfunction or IGBT over strong current protection diagnosis and solution ...
Page 46: ...44 9 2 7 Over voltage or too low voltage protection diagnosis and solution ...