30
This indicator appears only when the compressor is in operation and indicates the current operating
frequency.
8.3 Main Protection
8.3.1 Three Minutes Delay at restart for compressor.
---- 1 minute delay for the 1st time start-up and 3 minutes delay for others.
8.3.2 Temperature protection of compressor top.
---- Top temp. protector cut off for 30s and restart the compressor with 3 minutes delay.
8.3.3 Temperature protection of compressor discharge.
----When the compressor discharge temp. is getting higher, the running frequency will be limited as
below rules:
----Compressor discharge temp. T5>115 for 5s, compressor stops.
---- 108<T5<115 , decrease the frequency to the lower level every 3 minutes.
-----90<T5<105 , keep running at the current frequency.
-----T5<90 , no limit for frequency.
8.3.4 Fan Speed is out of control.
----When Indoor Fan Speed keeps too low or too high for certain time, the unit will stop and the LED
will display the failure
8.3.5 Inverter module Protection.
----The Inverter module itself has a protection function against current, voltage and temperature. If
these protections happen, the corresponding code will display on indoor unit.
8.3.6 Indoor fan delayed open function
----When the system starts up, the louver will be active immediately and the indoor fan will open 10s
later.
8.3.7 Compressor preheating functions.
----Preheating permitting condition:
If T4(outdoor ambient temperature)
3 and the machine connects to power supply newly or if T4
3 and compressor has stopped for over 3 hours, the compressor heating cable will work.
----Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of compressor, then the
compressor is heated without operation.
Summary of Contents for BIN312C2V31
Page 1: ...CSI 1206 A SERVICE MANUAL BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 AIR CONDITIONER ...
Page 12: ...10 Model R mm L mm H mm Dimension of installation hole mm BIN625C2V31 106 5 70 45 65 ...
Page 16: ...14 5 Wiring Diagram 5 1 Indoor Unit BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 ...
Page 17: ...15 5 2 Outdoor Unit BIN312C2V31 BIN520C2V31 ...
Page 18: ...16 BIN625C2V31 BIN414C2V31 202037391056 ...
Page 40: ...38 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution ...
Page 41: ...39 9 2 2 Indoor outdoor units communication protection diagnosis and solution ...
Page 42: ...40 9 2 3 Zero crossing signal diagnosis and solution ...
Page 43: ...41 9 2 4 Indoor fan speed has been out of control diagnosis and solution ...
Page 44: ...42 9 2 5 Open or short circuit of temperature sensor diagnosis and solution ...
Page 45: ...43 9 2 6 IPM malfunction or IGBT over strong current protection diagnosis and solution ...
Page 46: ...44 9 2 7 Over voltage or too low voltage protection diagnosis and solution ...