Innova Srl
Page 26
N420740A _manuale-SLC+ 2022
multi_EN_Rev.01.docx
MODBUS RTU CONNECTION TO THE UNIT
Without connecting the display, the machine
can be connected to a Modbus RS485 RTU
supervision system;
The communication protocol is:
RTU 9600 N 8 1;
Screw terminals
Recommended cable = 2x0.5 mm shielded
Modbus RTU unit connection
MODBUS RTU CONNECTION TO REMOTE PANEL T / H
With the connection of the remote panel, the
machine can be connected to a supervision
system directly on the control panel which
becomes a slave of a supervision system;
There are two terminals A and B in order to
comfortably carry out the in and out
connection;
The communication protocol is:
RTU 9600 N 8;
Screw terminals
Recommended cable = 2x0.5 mm shielded
Modbus RTU control panel connection