Innova Srl
Page 11
N420740A _manuale-SLC+ 2022
multi_EN_Rev.01.docx
Do not mount the unit with sides or surfaces in direct
contact with the walls to avoid possible contact noises,
insert rubber or neoprene strips in this case.
Ceiling mount
2.3
CONDENSATE DRAIN CONNECTION
For the heat recovery unit to function correctly, a condensate drain must be connected to the plumbing system (drain) of the house.
Furthermore, to allow the condensate water to flow correctly and avoid unpleasant odors, the condensate drain must always be equipped
with the appropriate siphon to be placed on the drain line by the installer;
To install the condensate drain, comply with the following
standards:
•
give a slope of at least 2% to the exhaust pipe;
•
provide for the possibility of disconnecting the drain
hose for any maintenance (in particular in the case of
ceiling installation);
•
make sure that the discharge end of the pipe is at
least below the water level of the siphon;
•
make sure that the siphon is always full of water.
In horizontal positioning the drain is 18 mm in diameter;
Horizontal installation drain