INSTALLATION
2.1
INSTALLATION CONDITIONS
The unit must be installed according to national and local standards that regulate the use of electrical devices and according to the following
indications:
•
install the unit inside residential buildings with an ambient temperature between 3 ° C and 45 ° C;
•
avoid areas near sources of heat, steam, flammable and / or explosive gases and particularly dusty areas;
•
install the unit in a place not subject to frost (the condensation water must be drained not frozen, at a certain inclination, using a
siphon;
•
do not install the unit in areas with a high relative humidity rate (such as a bathroom or toilet) to avoid condensation on the
external surface;
•
choose an installation site where there is sufficient space around the unit for the connections of the air ducts and to be able to
carry out maintenance operations;
•
the consistency of the ceiling / wall / floor where the unit will be installed must be adequate for the weight of the unit and not
cause vibrations.
The environment chosen for the installation must contain:
•
connections of the air ducts;
•
230 V single-phase electrical connection
•
connection for condensate drain
•
water inlet and outlet water connection
2.2
UNIT POSITIONING
Ceiling mount
To mount the unit on the ceiling, you need:
•
Use the 4 mounting holes on the top of the unit.
•
Fix the unit to the ceiling, using the brackets, using
suitable anchoring systems (dowels, threaded bars,
chains…) and check the leveling with the help of a
level.
•
Ensure sufficient space for carrying out
maintenance activities: the opening of the unit
cover (from below) and accessibility to the
electrical box and to the hydraulic connections
must be guaranteed;