Inis Oirr MK2 Multifuel Boiler stove
9
Installation Manual
Specification
Output Kw
Water Kw
14
8.5
Flue Dia mm
153
Flue Gas
Temperature
266
Fuel
Wood, eco
fuels, peat
dried,
smokeless
coal
Min distance to
combustibles
Rear mm
Sides mm
150
250
CO @ 13%O2 %
0.14
Stove Mass
KG
165
Max Hearth Temp
52
Installation Instructions
The heat outputs as shown above were
obtained using well-seasoned hardwood
using a refuelling time of 1.5 hrs.
The wooden crating the stove was shipped
in can be cut up for fuel in the stove.
Health and Safety
precautions
Please ensure that the installation of
the stove complies with all the
requirements of the relevant Health and
safety at work acts applicable.
Some materials used in fire cement are
caustic and contact with the skin should
be avoided. In case of contact with the
skin wash with plenty of cold water.
If any structural work is required for
installation please take note of the
possible presence of asbestos. If the
presence of asbestos is found please
contact a registered asbestos removal
firm.
Combustion and
ventilation air
requirements
Proper air supply must be insured to the
room into which the stove is to be
installed. A permanent vent opening with
a minimum free area of 65 cm sq. must be
present and ensure that the vent cannot
be blocked for example by fallen leaves
and that any grills that fit the vent do
not lessen the cross section of the
vent. Under no circumstances should
there be an extractor fan in the same
room as the stove, to avoid the
possibility of combustion gases being
drawn into the room.