Programming manual
Programming the system
27
Chapter 9
Programming the system
9.1
Setting the Time and Date
From panel:
<key>, Maintenance, <code>, DATE / TIME,
or:
<key>, 7, <code>, 5
This option allows you to set the Time and Date on the control panel clock and select the date format
(European, British and ISO) that will be used on the displays, in the events log and by the timers.
Attention:
If you are dealing with several control panels in a network, it is advisable to set the Date and
Time via computer, this method will align all the control panels in the network.
The control panel which operates as the “system clock” synchronizes all the clocks of the control panels in
the network. You should avoid setting the date and time separately on each control panel, as the settings
will be deleted at the successive alignment, that is, unless the settings are implemented by the control
panel that manages the “system clock”.
Complete all fields.
Press
to confirm the data entry.
The confirm screen will appear.
9.2
Defining the access codes
This option allows you to define the control panel access codes used by authorized security personnel to
access the reserved functions.
The defined user levels established by the law which governs the persons responsible for the installed
system (level 2) and for the Installers and Maintenance technicians (level 3), have been further divided
into Users and Authorized users (for level 2) and Installer or Maintenance technician (for level 3), thus
creating four different access levels.
Each control panel manages 10 access codes which can be assigned to any one of the previously mentioned
access levels.
Refer to the installation manual paragraph
2.4 - Operator classification - Access Levels
.
From panel:
<key>, Programming, <code>, Access Codes, xxx Code,
or:
<key>, 8, <code>, 7, xxx
Level
Users
Jumper
Keyswitch
Default code
1
The public
No
No
No
2
User
No
Position “LEV.2”
00001
2
Authorized user
No
Position “LEV.2”
00002
3
Maintenance
To be inserted
No
00003
4
Installer
To be inserted
No
00004
D A T E F o r m a t : E U R O P E d d / m m / y y
T I M E : 0 0 : 0 0
D A Y : 0 0 M O N T H : 0 0
Y E A R : 0 0