ABX2011IQM01_ - Installation and Operation Manual
10. Unit disconnection
This section details the procedure to disconnect the charging station. If you want to operate inside the unit, it is
mandatory to follow these instructions in the same order in which they appear here to remove tension.
1. If there is an active charging process, end the charging session.
2. Press the emergency button.
3. Remove DC voltage from a means of disconnection external to the unit.
4. Remove AC voltage from a disconnecting means external to the unit.
5. Wait 10 minutes for the existing internal capacitances to discharge, for the internal elements to cool, and
for the residual movement of the fan blades to stop.
6. Open the unit and, with the appropriate PPE, check the absence of voltage in the AC connection.
7. Mark the cutting area with a sign saying ¨
Attention, maneuvering prohibited…
¨. If necessary, delimit the
work area.
41
Unit disconnection