Features and Functions
S01 - Ct Real Time Clock Set
Adjustment for the internal real time clock.
(Hours, Minutes, Date, Month, Year)
The ‘Day of the Week’ (1= Monday to 7=Sunday) is
automatically calculated and set in accordance with
the Day, Month and Year.
The default setting for this
parameter is - --.--. (Represents the clock has not been
initialized))
The values for this parameter are:
“1” to “7” the ‘Day of the Week’ (1= Monday to
7=Sunday) which is automatically calculated and
set in accordance with the Day, Month and Year
entered.
“00” to “23” the Hour for the Real Time Clock.
“0” to “59” the Minutes for the Real Time Clock.
“1” to “31” the Day for the Real Time Clock.
“1” to “12” the Month for the Real Time Clock.
“2005” to “2100” the Year for the Real Time Clock.
S02
12
02
03
04
ER
NC
PM
CF
psi
X
4
145
X
01 P>
psi
Pressure Control; Tables
S02 - NC Number of Compressors
This parameter sets the number of compressors
connected to, and controlled by, the x8I or x12I. This
value must be set to match the system at commissioning.
The default setting for this parameter is 4.
The values
for this parameter are:
“1” for 1 compressor
To
“8” for 8 compressors (x8I)
“12” for 12 compressors (x12I)
S02 - PM Maximum Pressure Alarm
This parameter sets the High pressure ‘Fault’ level. This
value remains active at all times and is the same for all
‘Tables’. It should be set just below system pressure relief
value(s) and below the maximum system pressure rating
of all air system components.
The default setting for
this parameter is 145.
The values for this parameter are:
The highest value for the Maximum Pressure Alarm
setpoint = “The maximum range of the pressure
transducer used”
The lowest value for the Maximum Pressure Alarm
setpoint = “The highest value from any Table “PH
- Pressure High” Setpoint plus 2 times the “To
– Tolerance”
If PH in Table 1 (T01) is set for 100 PSI, and PH in
Table 2 (T02) is set for 110 and TO is set for 3.0
PSI, then the lowest Maximum Pressure setpoint
would be 116 PSI.