RT-SVF69C-EN
7
General Data
Table 3.
General data — heating — 12½ tons with eFlex™ technology
12.5 Tons Downflow & Horizontal Units
Heating Performance (Gas/Electric Only)
(a)
Heating Models
Low
High
Modulating Turn Down =
2.5:1
Heating Input (Btu/h)
150,000
250,000
350,000
1st Stage (Btu/h)
100,000
175,000
140,000
Heating Output (Btu/h)
122,000
203,000
283,500
1st Stage (Btu/h)
81,000
142,000
113,400
AFUE% (DF/HZ)
(b)
Downflow/Horizontal
81.0 / 81.0
80.7 / 79.9
80.1 / 79.1
Steady State Efficiency %
81
81
81
No. Burners
1
1
1
No. Stages
2
2
N/A
Gas Supply Line Pressure
(in. wc)
2.5 / 14.0
2.5 / 14.0
2.5 / 14.0
Natural Only
Natural or LP (minimum/
maximum)
Gas Connection Pipe Size
(in.)
1/2
1/2
3/4
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American
National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings
should be reduced at the rate of 4% for each 1000 feet above sea level.