Ingersoll-Rand Voyager TZ 150F Series Service Facts Download Page 14

14

 RT-SVF69C-EN

Sequence of Operation

Single Zone Variable Air Volume 
(Single Zone VAV) Control

For normal Cooling operation, available cooling capacity 
will be modulated in order to meet the calculated 
discharge air setpoint between the user selected upper 
and lower limits. If the current active cooling capacity is 
controlling the discharge air within the deadband no 
additional Cooling capacity change will be requested. As 
the Discharge Air Temperature rises above the deadband 
the control will request additional capacity as required 
(additional compressor operation or economizer). As the 
Discharge Air Temperature falls below the deadband the 
algorithm will request a reduction in active capacity. 

Cooling Operation

If the control determines that there is a need for 
compressor operation in order to meet the discharge air 
requirements, once supply fan proving has been made, 
the unit will begin to modulate compressors. As the zone 
cooling demand continues to increase, if additional 
capacity is required, the supply fan output will be 
modulated above minimum speed in order to meet the 
zone requirements. 

Note:

The supply fan speed will remain at the activated 
compressors’ associated minimum value until the 
control requires additional capacity to meet the 
zone demand. 

As the cooling load in the zone decreases the control will 
reduce the speed of the fan down to minimum per 
compressor operation and control the compressor 
outputs accordingly. As the compressors begin to de-
energize, the Supply Fan speed will fall back to the Cooling 
Capacity's associated minimum fan speed but not below. 
As the load in the zone continues to drop, cooling capacity 
will be reduced in order to maintain the calculated 
discharge air setpoint. 

Economizer Cooling

During normal Economizer Cooling, the fan speed will 
operate at its minimum. However, if the economizer is able 
to meet the demand alone, due to desirable ambient 
conditions, the supply fan speed will be allowed to 
increase above the minimum prior to utilizing mechanical 
cooling. Note that Economizer Enable/Disable decisions 
will be made based on the previous sections; however, the 
economizer control point will now be variable based on 
the zone cooling demand.

Demand Controlled Ventilation

Units configured for SZVAV and Demand Controlled 
Ventilation (CO

2

 sensor value available) require a new 

control scheme comprised of 2 existing schemes that have 
been traditionally mutually exclusive; DCV and OA CFM 
Compensation. Units configured with DCV will invoke the 
new Demand Controlled Ventilation scheme which allows 

variable Bldg. Design and DCV Minimum Positions and OA 
Damper Position Target setpoints based on the supply fan 
speed and space CO

2

 requirements.

Economizer Damper Position Set-Up with 
DCV

This new scheme will require the setting of 5 OA Damper 
position setpoints; 3 more than on non-SZ VAV. These new 
setpoints are located on the RTVM module:

1.

Design Min Position @ Minimum Fan Speed 
Command (RTVM R130)

2. Design Min Position @ Middle Fan Speed Command 

(RTVM R136)

3. Design Min Position @ Full Fan Speed Command 

(RTEM Design Min Position)

4. DCV Min Position @ Minimum Fan Speed Command 

(RTVM R41)

5. DCV Min position @ Full Fan Speed Command (RTEM 

DCV Min Position)

As the supply fan speed command varies between 
minimum and maximum, the Building Design and DCV 
Minimum Position Targets will be calculated between the 
user selected setpoints based on the instantaneous supply 
fan speed. The Bldg. Design and DCV Minimum Position 
Targets will be used to calculate the Active OA Damper 
Minimum Position Target, as on traditional units, based on 
the Space CO2 relative to the active Design and DCV CO2 
setpoints. 

By default, the Design Minimum Position schedule will be 
a linear line through all user selectable Design Minimum 
Position setpoints. The user will have the ability to set the 
Design Minimum Position at Middle fan speed command 
to a point that would be lower than the calculated linear 
line between the Design Minimum Position setpoints at 
0% and 100% fan speed command in order to compensate 
for the non-linear outside airflow through the fan and 
damper modulation range. However, if the Design 
Minimum Position at Middle fan speed command is set to 
a point that would be higher than the calculated linear line 
between the Design Minimum Position setpoints at 
Minimum and Full fan speed command, the minimum 
position will be limited to the point that would make the 
Design Minimum Position schedule linear.

Provisions have been made in Service Test Mode to allow 
for proper damper minimum position setup:

1.

To set the Design and DCV Minimum Position setpoints 
at Minimum Fan Speed, set the unit to operate at Step 
1 (Fan ON) or Step 2 (Economizer Open) and make the 
proper adjustments.

2. To set the Design Minimum Position setpoint at Middle 

Fan Speed, set the unit to operate at Step 3 (Cool 1) and 
make the proper adjustment.

Summary of Contents for Voyager TZ 150F Series

Page 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Page 2: ...ion which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage...

Page 3: ...rademarks of their respective owners Revision History Updated Performance Data section WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury All Inge...

Page 4: ...Heating 15 Low Ambient Operation 15 Clogged Filter Option 15 Ventilation Override 16 Emergency Stop 16 Phase Monitor 16 Low Pressure Control 16 High Pressure Cutout and Temperature Dis charge Limit 1...

Page 5: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F3 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Page 6: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F4 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Page 7: ...0 81 0 80 7 79 9 80 1 79 1 Steady State Efficiency 81 81 81 No Burners 1 1 1 No Stages 2 2 N A Gas Supply Line Pressure in wc 2 5 14 0 2 5 14 0 2 5 14 0 Natural Only Natural or LP minimum maximum Gas...

Page 8: ...43 2 08 762 2 22 779 2 37 796 2 52 813 2 67 4000 649 1 64 673 1 78 696 1 92 717 2 06 738 2 21 758 2 36 778 2 51 796 2 66 815 2 81 832 2 96 4500 662 1 87 686 2 02 709 2 18 731 2 33 752 2 49 772 2 65 79...

Page 9: ...98 747 2 11 766 2 25 783 2 40 800 2 55 816 2 70 4000 656 1 68 679 1 82 702 1 96 723 2 10 744 2 25 764 2 40 783 2 55 802 2 70 820 2 85 837 3 01 4500 670 1 92 694 2 08 717 2 23 738 2 39 759 2 55 780 2...

Page 10: ...ters a 2 MERV 8 Filter b 2 MERV 13 Filter b Std Economizer with OA RA Dampers c Low Leak Economizer with OA RA Dampers d Electric Heater Accessory kW e 100 OA 100 RA 100 OA 100 RA 5 12 14 27 36 54 72...

Page 11: ...control LPC1 the high pressure control HPC1 and the discharge line thermostat DLT1 are closed while simultaneously reducing the modulating compressor motor speed to allow a smooth transition in system...

Page 12: ...is running at its maximum capacity and the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open the RTRM energizes the second fix...

Page 13: ...r compartment protects against abnormally high leaving air temperatures The automatic reset fan fail limit located in the upper middle section of the indoor fan board protects against abnormally high...

Page 14: ...e a new control scheme comprised of 2 existing schemes that have been traditionally mutually exclusive DCV and OA CFM Compensation Units configured with DCV will invoke the new Demand Controlled Venti...

Page 15: ...heat units the unit will have the ability to control the discharge air temperature to the calculated discharge air heating setpoint in order to maintain the Zone Temperature to the Zone Heating setpo...

Page 16: ...rse rotation It has an operating input voltage range of 190 600 VAC and LED indicators for ON and FAULT There are no field adjustments and the module will automatically reset from a fault condition Lo...

Page 17: ...to set the supply air temperature below 50 F In cooling if supply air temperature is more than 3 5 degrees warmer than the selected temperature a stage of cooling will be turned On if available Then...

Page 18: ...ode or switched to the Cooling Mode the unit will revert to the cooling operation If an Occupied Heating Mode is selected the unit will only function within the DWU perimeters until the system is swit...

Page 19: ...l temperature swing of the discharge air will likely be greater Zone Temperature Unoccupied Heating While a building is in an unoccupied period as designated by a remote panel with night setback or IC...

Page 20: ...g mode Allow all compressors to run long enough for the pressures to stabilize 2 Measure the liquid line temperature of each circuit near the condenser coil after pressures stabilize 3 Measure the liq...

Page 21: ...105F OD Ambient 95 F OD Ambient 85 F OD Ambient 74 62 F ID WB DB 86 72 F ID WB DB 120F OD Ambient 115F OD Ambient Figure 2 Cooling cycle pressure curve system 2 100 200 300 400 500 600 700 100 120 14...

Page 22: ...ve curve value c OK if the sub cooling is within 5 F of the curve value 4 The standard superheat operating range for units with the standard offering thermal expansion valves is 16 F 24 F These superh...

Page 23: ...RT SVF69C EN 23 Refrigerant Circuit Figure 4 12 5 tons eFlex system schematic...

Page 24: ...and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingers...

Reviews: