Ingersoll-Rand Voyager TZ 150F Series Service Facts Download Page 19

RT-SVF69C-EN

19

Sequence of Operation

Table 16

 lists the selectable dry bulb values by 

potentiometer setting. 

2. Reference Enthalpy - controlling the economizer cycle 

by sensing the outdoor air humidity. 

Table 16

 lists the 

selectable enthalpy values by potentiometer setting. If 
the outside air enthalpy value is less than the selected 
value, the economizer is allowed to operate.

3. Comparative Enthalpy - By utilizing a humidity sensor 

and a temperature sensor in both the return air stream 
and the outdoor air stream, the economizer will be able 
to establish which conditions are best suited for 
maintaining the zone temperature, i.e., indoor 
conditions or outdoor conditions.

Off Mode

This mode is set at the zone sensor or by ICS. During this 
status, no heating, ventilation, or mechanical cooling is 
being performed. When switching the “System” selector 
to the “Off” mode from any other mode, any diagnostic 
data and diagnostic indication signal will be retained as 
long as the system remains in the “Off” status. Switching 
the “System” selector from the “Off” mode back to any 
other mode of operation will reset all diagnostics.

Heating Operation

Heating operation on units configured with Traditional 
Multi-Zone VAV control will utilize two separate control 
methodologies based on heating configurations. For all 
“Staged” Heating types (Electric and Gas), the unit will 
utilize 100% full airflow during all active heating periods 
like traditional Constant Volume units. If the unit has 
modulating heat, the unit can be made to do discharge 
heating with VAV control. This is done by placing by 
placing a contact closure across the “Changeover Input” 
on the RTAM. During this mode, the unit will heat to the 
Supply Air Heating Setpoint ± 3.5°F. During low load or low 
airflow conditions the actual temperature swing of the 
discharge air will likely be greater.

Zone Temperature - Unoccupied Heating

While a building is in an unoccupied period as designated 
by a remote panel with night setback or ICS, the necessary 
heating capacity will be controlled to maintain the zone 
temperature to within the unoccupied setpoint deadband. 
For traditional VAV systems, the VFD will operate at 100% 
during this mode. It will be necessary to drive VAV boxes 
to their maximum position through ICS programming or 

the factory provided VHR relay. For Modulating Gas Heat 
units, Full Airflow is not required but can be enabled by 
connecting the changeover mode input J5-1 and J5-2 on 
the RTAM module. For all Staged Heating types, the 
Supply Fan will be controlled at maximum fan speed 
during active heating operation as during Occupied 
periods.

Gas Heat Control 

The ignition sequence and timing are provided by a 
separate heat control module. The RTRM only provides 
the heating outputs to initiate 1

st

 and 2

nd

 stages and 

control the combustion blower relay. Both stages of the 
furnace will start and operate for one minute and then 
cycle back if only one stage is required. Units with 
modulating heat capabilities will light on high fire for one 
minute and then modulate to the appropriate heating rate 
for the building load present.

Electric Heat Control

The RTRM provides two heating outputs for 1st and 2nd 
stages that will be controlled with at least a 10 seconds 
delay between each stage. When the fan selection switch 
is in the “AUTO” mode, the fan will start approximately 1 
second before the 1st heater stage is activated. The fan 
and heater will cycle off after the heating setpoint has been 
satisfied. Once the Zone Heating requirements have been 
satisfied, the fan and heat outputs will be controlled off.

Table 16. Economizer configuration 

Selection

Dry Bulb

Enthalpy Value

A

73°F

27 BTU/LB Air

B

70°F

25 BTU/LB Air

C

67°F

23 BTU/LB Air

D

63°F

22 BTU/LB Air

E

55°F

19 BTU/LB Air

Summary of Contents for Voyager TZ 150F Series

Page 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Page 2: ...ion which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage...

Page 3: ...rademarks of their respective owners Revision History Updated Performance Data section WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury All Inge...

Page 4: ...Heating 15 Low Ambient Operation 15 Clogged Filter Option 15 Ventilation Override 16 Emergency Stop 16 Phase Monitor 16 Low Pressure Control 16 High Pressure Cutout and Temperature Dis charge Limit 1...

Page 5: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F3 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Page 6: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F4 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Page 7: ...0 81 0 80 7 79 9 80 1 79 1 Steady State Efficiency 81 81 81 No Burners 1 1 1 No Stages 2 2 N A Gas Supply Line Pressure in wc 2 5 14 0 2 5 14 0 2 5 14 0 Natural Only Natural or LP minimum maximum Gas...

Page 8: ...43 2 08 762 2 22 779 2 37 796 2 52 813 2 67 4000 649 1 64 673 1 78 696 1 92 717 2 06 738 2 21 758 2 36 778 2 51 796 2 66 815 2 81 832 2 96 4500 662 1 87 686 2 02 709 2 18 731 2 33 752 2 49 772 2 65 79...

Page 9: ...98 747 2 11 766 2 25 783 2 40 800 2 55 816 2 70 4000 656 1 68 679 1 82 702 1 96 723 2 10 744 2 25 764 2 40 783 2 55 802 2 70 820 2 85 837 3 01 4500 670 1 92 694 2 08 717 2 23 738 2 39 759 2 55 780 2...

Page 10: ...ters a 2 MERV 8 Filter b 2 MERV 13 Filter b Std Economizer with OA RA Dampers c Low Leak Economizer with OA RA Dampers d Electric Heater Accessory kW e 100 OA 100 RA 100 OA 100 RA 5 12 14 27 36 54 72...

Page 11: ...control LPC1 the high pressure control HPC1 and the discharge line thermostat DLT1 are closed while simultaneously reducing the modulating compressor motor speed to allow a smooth transition in system...

Page 12: ...is running at its maximum capacity and the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open the RTRM energizes the second fix...

Page 13: ...r compartment protects against abnormally high leaving air temperatures The automatic reset fan fail limit located in the upper middle section of the indoor fan board protects against abnormally high...

Page 14: ...e a new control scheme comprised of 2 existing schemes that have been traditionally mutually exclusive DCV and OA CFM Compensation Units configured with DCV will invoke the new Demand Controlled Venti...

Page 15: ...heat units the unit will have the ability to control the discharge air temperature to the calculated discharge air heating setpoint in order to maintain the Zone Temperature to the Zone Heating setpo...

Page 16: ...rse rotation It has an operating input voltage range of 190 600 VAC and LED indicators for ON and FAULT There are no field adjustments and the module will automatically reset from a fault condition Lo...

Page 17: ...to set the supply air temperature below 50 F In cooling if supply air temperature is more than 3 5 degrees warmer than the selected temperature a stage of cooling will be turned On if available Then...

Page 18: ...ode or switched to the Cooling Mode the unit will revert to the cooling operation If an Occupied Heating Mode is selected the unit will only function within the DWU perimeters until the system is swit...

Page 19: ...l temperature swing of the discharge air will likely be greater Zone Temperature Unoccupied Heating While a building is in an unoccupied period as designated by a remote panel with night setback or IC...

Page 20: ...g mode Allow all compressors to run long enough for the pressures to stabilize 2 Measure the liquid line temperature of each circuit near the condenser coil after pressures stabilize 3 Measure the liq...

Page 21: ...105F OD Ambient 95 F OD Ambient 85 F OD Ambient 74 62 F ID WB DB 86 72 F ID WB DB 120F OD Ambient 115F OD Ambient Figure 2 Cooling cycle pressure curve system 2 100 200 300 400 500 600 700 100 120 14...

Page 22: ...ve curve value c OK if the sub cooling is within 5 F of the curve value 4 The standard superheat operating range for units with the standard offering thermal expansion valves is 16 F 24 F These superh...

Page 23: ...RT SVF69C EN 23 Refrigerant Circuit Figure 4 12 5 tons eFlex system schematic...

Page 24: ...and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingers...

Reviews: