Ingersoll-Rand Voyager TZ 150F Series Service Facts Download Page 18

18

 RT-SVF69C-EN

Sequence of Operation

Zone Temperature Control without 

 

a Night Setback Panel or ICS - Unoccupied 
Cooling 

When a field supplied occupied/unoccupied switching 
device is connected between RTRM J6-11 and RTRM J6-12, 
both the economizer and the mechanical cooling will be 
disabled.

Zone Temperature Control without 

 

a Night Setback Panel or ICS - Unoccupied 
Heating 

When a field supplied occupied/unoccupied switching 
device is connected between RTRM J6-11 and J6-12 and 
DWU is enabled, the zone temperature will be controlled at 
10°F below the Morning Warm-up setpoint, but not less 
than 50°F, by cycling one or two stages of either gas or 
electric heat, whichever is applicable.

Morning Warm-up (MWU) Control

Morning Warm-up is activated if the zone temperature is at 
least 1.5°F below the MWU setpoint whenever the system 
switches from Unoccupied to Occupied status. The MWU 
setpoint may be set from the unit mounted potentiometer 
or a remotely mounted potentiometer. The setpoint 
ranges are from 50°F to 90°F. When the zone temperature 
meets or exceeds the MWU setpoint, the unit will switch to 
the “Cooling” mode. The economizer will be held closed 
during the morning warm-up cycle.

Daytime Warm-up (DWU) Control

Daytime Warm-up is applicable during occupied status 
and when the zone temperature is below the initiation 
temperature. It can be activated or deactivated through 
ICS or a night setback zone sensor. If ICS or a night setback 
zone sensor is not utilized, DWU can be activated by 
setting the DWU enable DIP switch (RTAM) to ON and 
supplying a valid morning warm-up setpoint. The unit is 
shipped with a Morning Warm-up setpoint configured and 
the Daytime Warm-up function is activated (switch on). 
Opening the DWU enable switch will disable this function. 
If the system control is local, the DWU initiation setpoint is 
3°F below the Morning Warm-up setpoint. The termination 
setpoint is equal to the Morning Warm-up setpoint. If the 
system control is remote (Tracer™), the DWU setpoint is 
equal to the Tracer Occupied heating setpoint. The 
initiation and termination setpoints are selectable 
setpoints designated by Tracer. When the zone 
temperature meets or exceeds the termination setpoint 
while the unit is in an Occupied, “Auto” Mode or switched 
to the “Cooling” Mode, the unit will revert to the cooling 
operation. If an Occupied “Heating” Mode is selected, the 
unit will only function within the DWU perimeters until the 
system is switched from the “Heat” Mode or enters an 
Unoccupied status.

Note:

When a LCI is installed on a VAV unit, the MWU 
setpoint located on the RTAM board is ignored. The 

MWU and DWU setpoints come from the higher 
priority LCI-R DAC.

Supply Duct Static Pressure Control 

The supply duct static pressure is measured by a 
transducer with a 0.25 to 2.125 Vdc proportional output 
which corresponds to an adjustable supply duct static 
pressure of 0.3" w.c. to 2.5" w.c. respectively with a 
deadband adjustment range from 0.2" w.c. to 1.0" w.c. The 
setpoint is adjustable on the RTAM Static Pressure 
Setpoint potentiometer or through ICS.

Example:

 

Supply Duct Static setpoint = 2.0" w.c. (RTAM)

 

Deadband = 0.2" w.c. (RTAM)

 

Duct Static Control Range = 1.9" w.c. to 2.1" w.c. 

Mechanical Cooling with an Economizer

The economizer is utilized to control the zone temperature 
when the outside air conditions are suitable. The method 
used to determine economizer effectiveness, depending 
on the available data, is described below in descending 
order of complexity.

The most sophisticated method available is always used. 
Two of the three methods for determining the suitability of 
the outside air can be selected utilizing the potentiometer 
on the Economizer Actuator, as described below: 

1.

Ambient Temperature - controlling the economizing 
cycle by sensing the outside air dry bulb temperature. 

Table 14. Variable air volume mode operation

System Mode

Fan “Auto”

Fan “On”

Heat

DWU Active
DWU Off

DWU

2

Off

4

DWU

2

 

VAV Heating

4

 

Cool

VAV Cooling

1

VAV Cooling

1

Auto

DWU Active
DWU Off

DWU or 
Cooling

1,2,3,4

VAV Cooling

1

DWU or 
Cooling

1,2,3,4

VAV Cooling or 
Heating

1

Off

Off

4

 Off

4

 

Notes:

 1.

If Cooling is selected the supply fan will run continuously. If VAV 

Heating is activated the supply fan will run continuously.

 2.

If Daytime Warmup is Activated, the supply fan will run

     continuously.

 3.

Auto changeover between Cooling and Daytime

     Warmup depends upon the DWU initiate setpoint.

 4.

The fan will be Off any time the system selection switch

     is “Off”.

Table 15. Economizer effectiveness

Method used to determine 
economizer effectiveness

Required

Comparative Enthalpy

OAT, OAH, RAT, RAH

Reference Enthalpy

OAT, OAH

Reference Dry Bulb

OAT

Unable to determine effectiveness

OAT data is invalid or 
unavailable

Summary of Contents for Voyager TZ 150F Series

Page 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Page 2: ...ion which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage...

Page 3: ...rademarks of their respective owners Revision History Updated Performance Data section WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury All Inge...

Page 4: ...Heating 15 Low Ambient Operation 15 Clogged Filter Option 15 Ventilation Override 16 Emergency Stop 16 Phase Monitor 16 Low Pressure Control 16 High Pressure Cutout and Temperature Dis charge Limit 1...

Page 5: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F3 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Page 6: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F4 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Page 7: ...0 81 0 80 7 79 9 80 1 79 1 Steady State Efficiency 81 81 81 No Burners 1 1 1 No Stages 2 2 N A Gas Supply Line Pressure in wc 2 5 14 0 2 5 14 0 2 5 14 0 Natural Only Natural or LP minimum maximum Gas...

Page 8: ...43 2 08 762 2 22 779 2 37 796 2 52 813 2 67 4000 649 1 64 673 1 78 696 1 92 717 2 06 738 2 21 758 2 36 778 2 51 796 2 66 815 2 81 832 2 96 4500 662 1 87 686 2 02 709 2 18 731 2 33 752 2 49 772 2 65 79...

Page 9: ...98 747 2 11 766 2 25 783 2 40 800 2 55 816 2 70 4000 656 1 68 679 1 82 702 1 96 723 2 10 744 2 25 764 2 40 783 2 55 802 2 70 820 2 85 837 3 01 4500 670 1 92 694 2 08 717 2 23 738 2 39 759 2 55 780 2...

Page 10: ...ters a 2 MERV 8 Filter b 2 MERV 13 Filter b Std Economizer with OA RA Dampers c Low Leak Economizer with OA RA Dampers d Electric Heater Accessory kW e 100 OA 100 RA 100 OA 100 RA 5 12 14 27 36 54 72...

Page 11: ...control LPC1 the high pressure control HPC1 and the discharge line thermostat DLT1 are closed while simultaneously reducing the modulating compressor motor speed to allow a smooth transition in system...

Page 12: ...is running at its maximum capacity and the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open the RTRM energizes the second fix...

Page 13: ...r compartment protects against abnormally high leaving air temperatures The automatic reset fan fail limit located in the upper middle section of the indoor fan board protects against abnormally high...

Page 14: ...e a new control scheme comprised of 2 existing schemes that have been traditionally mutually exclusive DCV and OA CFM Compensation Units configured with DCV will invoke the new Demand Controlled Venti...

Page 15: ...heat units the unit will have the ability to control the discharge air temperature to the calculated discharge air heating setpoint in order to maintain the Zone Temperature to the Zone Heating setpo...

Page 16: ...rse rotation It has an operating input voltage range of 190 600 VAC and LED indicators for ON and FAULT There are no field adjustments and the module will automatically reset from a fault condition Lo...

Page 17: ...to set the supply air temperature below 50 F In cooling if supply air temperature is more than 3 5 degrees warmer than the selected temperature a stage of cooling will be turned On if available Then...

Page 18: ...ode or switched to the Cooling Mode the unit will revert to the cooling operation If an Occupied Heating Mode is selected the unit will only function within the DWU perimeters until the system is swit...

Page 19: ...l temperature swing of the discharge air will likely be greater Zone Temperature Unoccupied Heating While a building is in an unoccupied period as designated by a remote panel with night setback or IC...

Page 20: ...g mode Allow all compressors to run long enough for the pressures to stabilize 2 Measure the liquid line temperature of each circuit near the condenser coil after pressures stabilize 3 Measure the liq...

Page 21: ...105F OD Ambient 95 F OD Ambient 85 F OD Ambient 74 62 F ID WB DB 86 72 F ID WB DB 120F OD Ambient 115F OD Ambient Figure 2 Cooling cycle pressure curve system 2 100 200 300 400 500 600 700 100 120 14...

Page 22: ...ve curve value c OK if the sub cooling is within 5 F of the curve value 4 The standard superheat operating range for units with the standard offering thermal expansion valves is 16 F 24 F These superh...

Page 23: ...RT SVF69C EN 23 Refrigerant Circuit Figure 4 12 5 tons eFlex system schematic...

Page 24: ...and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingers...

Reviews: