Ingersoll-Rand Voyager TZ 150F Series Service Facts Download Page 20

20

 RT-SVF69C-EN

Pressure Curves

Refrigerant Charging Procedure

1.

Weigh the refrigerant charge into the liquid line 
Schrader fitting. Proper unit charge is listed on the unit 
serial data plate.

2. Liquid line charging is the preferred charging method 

to minimize starting the compressor with liquid 
refrigerant in the compressor oil sump. Never charge 
liquid into the low side of the system while the 
compressor is not operating. Never charge refrigerant 
into the compressor discharge schrader fitting.

3. R-410a must only be charged in the liquid state.

To Check Operating Pressures

1.

Enter the stage of the “Service Test Mode” of the unit 
that brings on all compressors in the cooling mode. 
Allow all compressors to run long enough for the 
pressures to stabilize.

2. Measure the liquid line temperature of each circuit 

near the condenser coil after pressures stabilize.

3. Measure the liquid line pressure of each circuit after 

pressures stabilize.

4. Use the chart below to plot the measurements taken 

and to determine any charge adjustment.

WARNING

Refrigerant under High Pressure!

System contains oil and refrigerant under high 
pressure. Recover refrigerant to relieve pressure before 
opening the system. See unit nameplate for refrigerant 
type. Do not use non-approved refrigerants, refrigerant 
substitutes, or refrigerant additives. Failure to recover 
refrigerant to relieve pressure or the use of non-
approved refrigerants, refrigerant substitutes, or 
refrigerant additives could result in an explosion which 
could result in death or serious injury or equipment 
damage. 

Summary of Contents for Voyager TZ 150F Series

Page 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Page 2: ...ion which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage...

Page 3: ...rademarks of their respective owners Revision History Updated Performance Data section WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury All Inge...

Page 4: ...Heating 15 Low Ambient Operation 15 Clogged Filter Option 15 Ventilation Override 16 Emergency Stop 16 Phase Monitor 16 Low Pressure Control 16 High Pressure Cutout and Temperature Dis charge Limit 1...

Page 5: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F3 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Page 6: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F4 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Page 7: ...0 81 0 80 7 79 9 80 1 79 1 Steady State Efficiency 81 81 81 No Burners 1 1 1 No Stages 2 2 N A Gas Supply Line Pressure in wc 2 5 14 0 2 5 14 0 2 5 14 0 Natural Only Natural or LP minimum maximum Gas...

Page 8: ...43 2 08 762 2 22 779 2 37 796 2 52 813 2 67 4000 649 1 64 673 1 78 696 1 92 717 2 06 738 2 21 758 2 36 778 2 51 796 2 66 815 2 81 832 2 96 4500 662 1 87 686 2 02 709 2 18 731 2 33 752 2 49 772 2 65 79...

Page 9: ...98 747 2 11 766 2 25 783 2 40 800 2 55 816 2 70 4000 656 1 68 679 1 82 702 1 96 723 2 10 744 2 25 764 2 40 783 2 55 802 2 70 820 2 85 837 3 01 4500 670 1 92 694 2 08 717 2 23 738 2 39 759 2 55 780 2...

Page 10: ...ters a 2 MERV 8 Filter b 2 MERV 13 Filter b Std Economizer with OA RA Dampers c Low Leak Economizer with OA RA Dampers d Electric Heater Accessory kW e 100 OA 100 RA 100 OA 100 RA 5 12 14 27 36 54 72...

Page 11: ...control LPC1 the high pressure control HPC1 and the discharge line thermostat DLT1 are closed while simultaneously reducing the modulating compressor motor speed to allow a smooth transition in system...

Page 12: ...is running at its maximum capacity and the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open the RTRM energizes the second fix...

Page 13: ...r compartment protects against abnormally high leaving air temperatures The automatic reset fan fail limit located in the upper middle section of the indoor fan board protects against abnormally high...

Page 14: ...e a new control scheme comprised of 2 existing schemes that have been traditionally mutually exclusive DCV and OA CFM Compensation Units configured with DCV will invoke the new Demand Controlled Venti...

Page 15: ...heat units the unit will have the ability to control the discharge air temperature to the calculated discharge air heating setpoint in order to maintain the Zone Temperature to the Zone Heating setpo...

Page 16: ...rse rotation It has an operating input voltage range of 190 600 VAC and LED indicators for ON and FAULT There are no field adjustments and the module will automatically reset from a fault condition Lo...

Page 17: ...to set the supply air temperature below 50 F In cooling if supply air temperature is more than 3 5 degrees warmer than the selected temperature a stage of cooling will be turned On if available Then...

Page 18: ...ode or switched to the Cooling Mode the unit will revert to the cooling operation If an Occupied Heating Mode is selected the unit will only function within the DWU perimeters until the system is swit...

Page 19: ...l temperature swing of the discharge air will likely be greater Zone Temperature Unoccupied Heating While a building is in an unoccupied period as designated by a remote panel with night setback or IC...

Page 20: ...g mode Allow all compressors to run long enough for the pressures to stabilize 2 Measure the liquid line temperature of each circuit near the condenser coil after pressures stabilize 3 Measure the liq...

Page 21: ...105F OD Ambient 95 F OD Ambient 85 F OD Ambient 74 62 F ID WB DB 86 72 F ID WB DB 120F OD Ambient 115F OD Ambient Figure 2 Cooling cycle pressure curve system 2 100 200 300 400 500 600 700 100 120 14...

Page 22: ...ve curve value c OK if the sub cooling is within 5 F of the curve value 4 The standard superheat operating range for units with the standard offering thermal expansion valves is 16 F 24 F These superh...

Page 23: ...RT SVF69C EN 23 Refrigerant Circuit Figure 4 12 5 tons eFlex system schematic...

Page 24: ...and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingers...

Reviews: