TK 56171-2-OP-EN
129
in the Defrost mode for 30 or 45 minutes (depending on setting).
Post Trip Checks
1.
Wash the unit.
2.
Check for leaks.
3.
Check for loose or missing hardware.
4.
Check for physical damage to the unit.
Enroute Inspections
Complete the following enroute inspection every four hours. This will help
minimize temperature related problems.
Inspection Procedure
1. Verify setpoint is correct.
2. Check the return air temperature reading. It should be within the desired
temperature range.
3. Initiate a manual defrost cycle after each enroute inspection.
Inspection Troubleshooting
1. If a temperature reading is not within the desired temperature range,
refer to the troubleshooting table (
). Correct problem as
required.
2. Repeat the Enroute Inspection every 30 minutes until the compartment
temperature is within the desired temperature range. Stop the unit if the
compartment temperature is not within the desired temperature range
on two consecutive 30 minute inspections, especially if the compartment
temperature appears to be moving away from the setpoint.
3. Immediately contact the nearest Thermo King Service Center or your
company office.
4. Take all necessary steps to protect and maintain proper load
temperature.