80446339 Rev E
EN-25
EN
•
PAGE 10: ANALOG OUTPUTS
Figure 34 : Analog Outputs
The value for the analog outputs will be in mA.
• VSD Blower Output
NOTICE
(RO) indicates read-only values.
FACTORY SETTINGS FOLDER
This folder is for factory and service personnel. A password must be entered
on page one in order to adjust values in this folder. This folder is used for
setting parameters that are specific to that compressor and displaying
software information for the controller.
•
PAGE 1: PASSWORD
Figure 35 : Password
Table 15 : Password
Display Text
Description
Password
Provides access to enter a valid password to gain access
to password protected parameters. The password is
entered by scrolling down to the password value and
pressing the RETURN key.
Password
Entered
This checkbox will indicate a valid password has been
entered. If this checkbox is blank, a valid password has
not been entered or it has timed out. This is read only.
Enable PW
Timeout
Checking this box will enable the password time feature.
Password
Timeout
This timeout along with the password timeout enable
allows the user to set an adjustable amount of time
to require a valid password to be re-entered. Once
this timeout is reached re-entry of a valid password is
required.
•
PAGES 2-5: FACTORY SETTINGS
Figure 36 : Factory Settings
These pages are used for setting parameters that are specific to the
compressor. All of the factory settings that are adjustable are listed below.
All settings on these pages are password protected.
• Rated Pressure (psi – 100, 115, 135, 190)
• Enable Two Stage (On/Off )
• Starter Type (Star-delta, Remote Starter, Soft Starter)
• Service Level (0, 1, or 2)
• Enable Modulation (On/Off )
• Enable PAC (On/Off )
RELEASED 01/Nov/2018 12:06:37 GMT