SS-SVX10H-EN
43
Pre-Start
Control Circuit Features
N
No
otte
e:: Not all of these features may be required for your
unit, check electrical schematic.
Discharge Temperature Limit (DTL)
The control’s sensor is located on the discharge line.
This device will shut off the compressor and the
outdoor fan(s) if the discharge temperature exceeds the
DTL setting. Once the discharge temperature has
returned to normal, the compressor will cycle back on.
Low Outdoor Ambient Cooling
The Evaporator Defrost Control is standard equipment
on Air Handlers and will permit low ambient cooling
down to 50°F. For cooling operation down to 0°F, use an
Accessory Head Pressure Control on the outdoor unit.
Evaporator Defrost Control (EDC)
This control is located in the Air Handler. The control’s
sensing tube is embedded vertically in the evaporator
coil, near the center. This device will stop the
compressor if the indoor coil temperature drops below
its setting. The indoor air will still circulate across the
coil bringing the temperature of the coil back up to the
cut-in temperature of the evaporator defrost control.
Low Pressure Cut-Out (LPCO)
This control’s sensor is located in the suction (gas) line,
near the compressor. This control will stop the
compressor and the outdoor fans if suction pressure
drops below the Low Pressure Cut-Out setting. Once
the suction pressure has returned to normal, the
compressor and outdoor fans will cycle back on.
High Pressure Cut-Out (HPCO)
This control’s sensor is located in the discharge line.
This device will shut off the compressor and the
outdoor fan(s) if the discharge pressure exceeds the
High Pressure Cut-Out’s setting. Once the discharge
pressure has returned to normal, the compressor will
cycle back on.
W
WA
AR
RN
NIIN
NG
G
P
Prre
ev
ve
en
ntt IIn
njju
urry
y!!
D
Du
ue
e tto
o a
ag
ge
en
nccy
y ssa
affe
etty
y rre
eq
qu
uiirre
em
me
en
ntts
s,, n
no
o ssc
ch
hrra
ad
de
err
cco
orre
e iiss tto
o b
be
e iin
ns
stta
alllle
ed
d b
be
en
ne
ea
atth
h tth
he
e H
HP
PC
CO
O.. R
Re
em
mo
ov
va
all
o
off tth
he
e H
HP
PC
CO
O w
wiitth
ho
ou
utt e
ev
va
accu
ua
attiin
ng
g tth
he
e ssy
ysstte
em
m cch
ha
arrg
ge
e
cco
ou
ulld
d cca
au
usse
e iin
njju
urry
y a
an
nd
d rre
elle
ea
asse
e o
off rre
effrriig
ge
erra
an
ntt..
Internal Overload Protector (IOL)
This device is embedded in the compressor. It will shut
off the compressor if the discharge temperature of the
compressor exceeds its design trip temperature.
N
No
otte
e:: The IOL will put the compressor back in
operation once the compressor motor heat has
dropped below the trip setting; however, a check
of the refrigerant and electrical systems should
be made to determine the cause and be
corrected.