Charging Levels
Table 4.
Estimated charge levels at ARI rated line lengths (25 feet) - 50 & 60 Hz
Matched Set
Refrigerant Charge
Per Circuit
Circuit 1
Circuit 2
Liquid Line Diameter
Vapor Line Diameter
TTA061G w/TWE076D
(a)
10
N/A
0.5 (1/2”)
1.125 (1 1/8”)
TTA061H w/TWE073E
7.0
7.0
0.5 (1/2”)
0.875 (7/8”)
TTA073G w/TWE090D
10
N/A
0.5 (1/2”)
1.125 (1 1/8”)
TTA073H w/TWE073E
7.0
7.0
0.5 (1/2”)
0.875 (7/8”)
TTA076G w/TWE076D
9.7
N/A
0.5 (1/2”)
1.375 (1 3/8”)
TTA076H w/TWE076E
7.25
7.3125
0.5 (1/2”)
1.125 (1 1/8”)
TTA090G w/TWE090D
9.7
N/A
0.5 (1/2”)
1.375 (1 3/8”)
TTA090H w/TWE090E
7.25
7.3125
0.5 (1/2”)
1.125 (1 1/8”)
TTA101G w/TWE101D
13.6
N/A
0.5 (1/2”)
1.375 (1 3/8”)
TTA101H w/TWE101E
7.7
7.6
0.5 (1/2”)
1.125 (1 1/8”)
TTA101J w/TWE101D
13.1
N/A
0.5 (1/2”)
1.375 (1 3/8”)
TTA120G w/TWE120D
13.6
N/A
0.5 (1/2”)
1.375 (1 3/8”)
TTA120H w/TWE120E
7.7
7.6
0.5 (1/2”)
1.125 (1 1/8”)
TTA120J w/TWE120D
13.1
N/A
0.5 (1/2”)
1.375 (1 3/8”)
TTA126H w/TWE126E
9.8
9.8
0.5 (1/2”)
1.125 (1 1/8”)
TTA150H w/TWE150E
9.8
9.8
0.5 (1/2”)
1.125 (1 1/8”)
TTA156H w/TWE156E
11.5
11.5
0.5 (1/2”)
1.375 (1 3/8”)
TTA156J w/TWE156E
21.3
N/A
0.625 (5/8”)
1.625 (1 5/8”)
TTA180H w/TWE180E
11.5
11.5
0.5 (1/2”)
1.375 (1 3/8”)
TTA180J w/TWE180E
21.3
N/A
0.625 (5/8”)
1.625 (1 5/8”)
TTA201H w/TWE201E
11.6
12.0
0.5 (1/2”)
1.375 (1 3/8”)
TTA201J w/TWE201E
23.8
N/A
0.625 (5/8”)