Configuration
9
Time required for mode change
Note:
Applies only when digit 3 is set to “1” (Auto
Changeover mode is enabled).
0: 5 minutes
1: 7 minutes
2: 9 minutes
3: 11 minutes
4: 13 minutes
5: 15 minutes
6: 20 minutes
7: 30 minutes
10
Compensation option for height or pipe length
difference between indoor units
0: Use default value
1: Use when height or pipe length difference is as specified.
(c)
2: Use when height or pipe length difference is as specified.
(d)
N/A
13
Factory set to 2
Cannot be changed. Not seen in configuration mode.
18
(e)
Control variables for auxiliary heat
N/A
19
Factory set to 3.
Cannot be changed. Not seen in configuration mode.
23
Forcing fan operation for heating and cooling
(a) Up to 8 IDUs can be accommodated on a single MCU port under the following conditions: IDUs cannot exceed 54 MBH, mode master control must be
used, wired controllers must be used.
(b) Cooling Only operation (HR only) must be selected on HR systems that have a direct connection (no MCU) to main liquid and gas lines.
Table 2.
Installation option #2: Digit 2 = 5 (continued)
Display
screen
(mode and
On/Off)
Digit
Option description
Set digit to...
Set temperature for auxiliary heat On
Time delay for auxiliary
heat On
0: No temperature offset
No delay
1: No temperature offset
10 minutes
2: No temperature offset
20 minutes
3: 2.7°F (1.5°C)
No delay
4: 2.7°F (1.5°C)
10 minutes
5: 2.7°F (1.5°C)
20 minutes
6: 5.4°F (3.0°C)
No delay
7: 5.4°F (3.0°C)
10 minutes
8: 5.4°F (3.0°C)
20 minutes
9: 8.1°F (4.5°C)
No delay
A: 8.1°F (4.5°C)
10 minutes
B: 8.1°F (4.5°C)
20 minutes
C: 10.8°F (6.0°C)
No delay
D: 10.8°F (6.0°C)
10 minutes
E: 10.8°F (6.0°C)
20 minutes
Note: If further temperature offsets are desired, contact technical
support.
Cooling: Fan Setting
Heating: Fan Setting
0: Disabled
Disabled
1: Disabled
Enabled (Fan: User setting)
2: Disabled
Enabled (Fan: High)
3: Disabled
Enabled (Fan: Low)
4: Enabled (Fan: user setting)
Disabled
5: Enabled (Fan: user setting)
Enabled (Fan: User setting)
6: Enabled (Fan: user setting)
Enabled (Fan: High)
7: Enabled (Fan: user setting)
Enabled (Fan: Low)
8: Enabled (Fan: High)
Disabled
9: Enabled (Fan: High)
Enabled (Fan: User setting)
A: Enabled (Fan: High)
Enabled (Fan: High)
B: Enabled (Fan: High)
Enabled (Fan: Low)
C: Enabled (Fan: Low)
Disabled
D: Enabled (Fan: Low)
Enabled (Fan: User setting)
E: Enabled (Fan: Low)
Enabled (Fan: High)
F: Enabled (Fan: Low)
Enabled (Fan: Low)