26
VRF-SVX26D-EN
Configuration
3
Evaporator drying
0: Disabled
1: Disabled
2: Enabled (5 min)
3: Disabled (5 min)
4: Enabled (10 min)
5: Disabled (10 min)
6: Enabled (30 min)
7: Disabled (30 min)
Note:
When Cooling or Dry mode stops, the indoor fan continues to operate for the
number of minutes indicated by each setting.
4
Remote temperature sensor/
minimizing fan operation when
unit is Thermo Off
5
Central control
0: Disabled
1: Enabled
6
RPM up
0: Disabled
1: Enabled
N/A
7
Factory set to 1
Cannot be changed. Not seen in configuration mode.
8
Drain pump
0: Disabled
1: Enabled (no delay)
2: Enabled (3-min delay)
11
Adjusted EEV position of
Thermo Off unit
0: Default EEV position
1: Reduced EEV position
N/A
13
Factory set to 2
Cannot be changed. Not seen in configuration mode.
14
External control relay
0: Disabled
1: On/off control
2: Off-only control
3: Window on/off control
Table 1.
Installation option #1: Digit 2 = 2 (continued)
Display
screen
(mode and
On/Off)
Digit
Option description
Set digit to...
Remote temperature sensor Minimizing fan operation when unit is Thermo Off
0: Disabled
Disabled
1: Enabled
Disabled
2: Disabled
Enabled (Heating)
(a)
3: Enabled
Enabled (Heating)
(a)
4: Disabled
Enabled (Cooling)
(a)
5: Enabled
Enabled
(Cooling)
(a)
6: Disabled
Enabled (Heating/Cooling)
(a)
7: Enabled
Enabled (Heating/Cooling)
(a)
8: Disabled
Enabled (Cooling Ultra Low Fan)
(a)
9: Enabled
Enabled (Cooling Ultra Low Fan)
(a)
A: Disabled
Enabled (Heating/Cooling Ultra Low Fan)
(a)
B: Enabled
Enabled (Heating/Cooling Ultra Low Fan)
(a)
(a)
Minimizes fan operation when unit is Thermo Off. Fan operates for 20 seconds
at an interval of 5 minutes in Heat mode. Fan stops or operates in Ultra Low in
Cooling mode when unit is Thermo Off.