28
VRF-SVX26D-EN
Configuration
Installation Option #2
When
digit 2
is set to a value of “
5
,” the options shown in
can be changed to the values in
the right column.
Table 2.
Installation option #2: Digit 2 = 5
Display
screen
(mode and
On/Off)
Digit
Option description
Set digit to...
N/A
1
Factory set to 0
Cannot be changed. Not seen in configuration mode.
2
Installation option #2
5
3
Auto Changeover (Heat Recovery or Cooling Only)
0: Follow product option
1: Auto Changeover enabled (see
).
(a)
2: Cooling Only enabled (see
(b)
4
Heating deadband
Note:
Applies only when digit 3 is set to “1”
(Auto Changeover mode is enabled).
0: Disabled
1: 0.9°F (0.5°C)
2: 1.8°F (1°C)
3: 2.7°F (1.5°C)
4: 3.6°F (2°C)
5: 4.5°F (2.5°C)
6: 5.4°F (3°C)
7: 6.3°F (3.5°C)
5
Cooling deadband
Note:
Applies only when digit 3 is set to “1”
(Auto Changeover mode is enabled).
0: Disabled
1: 0.9°F (0.5°C)
2: 1.8°F (1°C)
3: 2.7°F (1.5°C)
4: 3.6°F (2°C)
5: 4.5°F (2.5°C)
6: 5.4°F (3°C)
7: 6.3°F (3.5°C)
6
Standard for Auto Changeover (Heating to Cooling)
Note:
Applies only when digit 3 is set to “1”
(Auto Changeover mode is enabled).
0: 1.8°F (1°C)
1: 2.7°F (1.5°C)
2: 3.6°F (2°C)
3: 4.5°F (2.5°C)
4: 5.4°F (3°C)
5: 6.3°F (3.5°C)
6: 7.2°F (4°C)
7: 8.1°F (4.5°C)
N/A
7
Factory set to 1
Cannot be changed. Not seen in configuration mode.
8
Standard for Auto Changeover (Cooling to Heating)
Note:
Applies only when digit 3 is set to “1” (Auto
Changeover mode is enabled).
0: 1.8°F (1°C)
1: 2.7°F (1.5°C)
2: 3.6°F (2°C)
3: 4.5°F (2.5°C)
4: 5.4°F (3°C)
5: 6.3°F (3.5°C)
6: 7.2°F (4°C)
7: 8.1°F (4.5°C)