![Infranor XtrapulsCD1-pm User Manual Download Page 28](http://html.mh-extra.com/html/infranor/xtrapulscd1-pm/xtrapulscd1-pm_user-manual_2058369028.webp)
Chapter 4 - Programmation
28
XtrapulsCD1-pm - User manual
2.3
– MANUAL MOVEMENTS
There are 2 types of manual motion:
- manual positioning: moving of the motor until a given position via the serial link.
- manual jog: continuous movement when the JOG command is activated.
(JOG+ for a movement in the positive direction and JOG- for a movement in the negative direction)
The motion profile parameters are:
- motion speed,
- acceleration time,
- deceleration time.
The parameters
acceleration time
and
deceleration time
define the time with regard to the
maximum speed
parameter value. When the
motion speed
is lower than the maximum speed, the trajectory acceleration and
deceleration times are proportionally reduced.
Remark : The JOG deceleration time parameter value is also used when the STOP input is activated.
2.4
– BRAKE CONTROL AND AMPLIFIER DISABLING
Brake ON delay
: defines the time between the brake activation and the amplifier disabling according to the
following timing:
- brake ON (contact open),
- delay time,
- amplifier disabled.
The brake ON delay value must be higher than the brake response time.
Brake OFF delay
: defines the time between the amplifier enabling and the brake desactivation according to the
following timing:
- amplifier enabling,
- delay time,
- brake OFF (contact closed).
The brake off delay value must be higher than the amplifier servo loop response time.
Note: The brake ON and OFF delays are not valid for the stand-alone operation mode.
ENABLE input desactivation and fault reaction
defines the amplifier behaviour when the ENABLE input is
desactivated or when an amplifier fault is triggered:
- When
Switch off
is selected, the amplifier is immediately disabled and the motor is freewelling on ENABLE
input desactivation or on a fault reaction.
- When
Stop with current limit
is selected, the motor is first slowed down and then the amplifier disabled on
ENABLE input desactivation or a fault reaction.
Stop current limit
defines the current limitation value when the motor is slowed down on ENABLE input
desactivation or a fault reaction. This current limit value is also used for the motor slow-down when the hardware
limit switches are activated.
Remark: The motor slow down with current limit is only possible when the following faults are triggered:
Position
following error
,
I²t
,
Motor overtemperature
,
Fieldbus error
. When the other amplifier faults are triggered, the
motor cannot be slowed down with current limit and the amplifier is immediately disabled.
Note: When the stopping with current limit operation is executed on ENABLE input desactivation or on a fault
reaction, the motor brake is activated at the end of the deceleration phase, when the motor is stopped.
Maximum speed
Acceleration time
Deceleration time
Motion speed