![INFOSEC UPS SYSTEM E4 Evolution II + TT Series User Manual Download Page 140](http://html.mh-extra.com/html/infosec-ups-system/e4-evolution-ii-tt-series/e4-evolution-ii-tt-series_user-manual_2058270140.webp)
139
INFOSEC UPS SYSTEM
–
15, Rue du Moulin
–
44880 Sautron
–
France
–
www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82
–
fax : +33(0)2 40 94 29 51
–
–
02 19 AA 59 203 07
220/230/240VAC (Ph-N)
AC Voltage Regulation
< 1% Typical (balanced load) < 2% Typical (unbalanced load)
Frequency Ra (Synchronize range)
40Hz ~ 70Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
1 hour for 105 ~110%, 10 mins for 111~125%, 1 min for 126~150%, 200ms for
>150%
Battery mode
1 hour for 105 ~110%, 10 mins for 111~125%, 1 min for 126~150%, 200ms for
>150%
Current Crest Ratio
3:1 max
Harmonic Distortion
100% linear load: <2% 100% nonlinear load: <4%
Transfer
Time
Line
Battery
0 ms
Inverter
Bypass
Synchronous transfer: <= 0ms Asynchronous transfer: < 1 cycle
Inverter
ECO
<20 ms
EFFICIENCY
AC mode
94%, Line mode @ 100% R Load
93.5%, Line mode @ 50% R Load
ECO Mode
98%, ECO Mode @ 100% R Load
97%, ECO Mode @ 50% R Load
Battery Mode
93 %, Battery mode @ 100% R Load
92.5%, Battery mode @ 50% R Load
BATTERY
Type
Depending on applications
Numbers
32 36 40 (adjustable)
Maximum charging current*
24A**
32A**
40A**
48A**
Floating Voltage
2.29V/cell
Boost Charging
2.35V/cell
Charger Voltage Regulation
< 1%
Ripple Voltage
< 1%
Ripple Current (% C10)
< 5
PHYSICAL
Dimension D X W X H mm
945 x 567 x 1015
995 x 567 x 1455
Dual Input
Model
Net Weight(kg)
197
232
309
343
ENVIRONMENT