18: Display setting for autonomy time
Interface
Setting
Parameter 2:
Set up the display setting for autonomy time
EAT:
If EAT is selected, it will display the remaining
autonomy time. (Default)
RAT:
If RAT is selected, it will show accumulated autonomy
time so far.
19: Acceptable input voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point and
acceptable low voltage point for input voltage range by
pressing the Down key or Up key.
HLS:
Input high voltage point
For 200/208/220/230/240 VAC models:
280/290/300:
setting the high voltage point in parameter 2.
(Default: 300Vac)
For 100/110/115/120/127 VAC models:
140/145/150:
setting the high voltage point in parameter 2.
(Default: 150Vac)
LLS:
Bypass low voltage point
For 200/208/220/230/240 VAC models:
110/120/130/140/150/160:
setting the low voltage point in
parameter 2. (Default: 110Vac)
For 100/110/115/120/127 VAC models:
55/60/65/70/75/80:
setting the low voltage point in
parameter 2. (Default: 55Vac)
00: Exit setting
Interface
Setting
Exit the setting mode.
Disconnect AC input and wait until the LCD display is off. The new setting will be activated when turning
on the UPS again.