INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - [email protected] – 07 19 AA 59 203 14
80
7. Specifications
MODEL
E7 One 1000 RT E7 One 1500 RT E7 One 2000 RT E7 One 3000 RT
CAPACITY*
1000VA/1000W
1500VA/1500W
2000VA/2000W
3000VA / 3000W
INPUT
Voltage
Range
Low Line
Transfer
160VAC/140VAC/120VAC/110VAC ± 5 % or 80VAC/70VAC/60VAC/55VAC ± 5 %
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line
Comeback
175VAC/155VAC/135VAC/125VAC ± 5 % or 87VAC/77VAC/67VAC/62VAC ± 5 %
High Line
Transfer
300 VAC ± 5 % or 150 VAC ± 5 %
High Line
Comeback
290 VAC ± 5 % or 145 VAC ± 5 %
Frequency Range
40Hz ~ 70 Hz
Phase
Single phase with ground
Power Factor
≧
0.99 @ full load
THDi
≦
5% @ 205-245VAC or 100~130VAC
THDU < 1.6% @ input and full linear load condition
OUTPUT
Output voltage
200/208/220/230/240VAC or 100/110/115/120/127 VAC
AC Voltage
Regulation
± 1% (Batt. Mode)
Frequency Range
(Synchronized
Range)
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
Current Crest Ratio
3:1
Harmonic Distortion
≦
2 % THD (Linear Load) ; 4 % THD (Non-linear Load)
Transfer
Time
AC Mode
to Batt.
Mode
Zero
Inverter to
Bypass
< 4 ms
Waveform (Batt.
Mode)
Pure Sinewave
EFFICIENCY
AC Mode
≧
89% @ full charged battery
≧
91% @ full charged battery
ECO Mode
≧
96% @ full charged battery
Battery Mode
≧
88%
≧
90%
BATTERY
Battery Type
12V/9AH
12V/9AH
12V/9AH
12V/9AH
Numbers
2
3
4
6
Recharge Time
3 hours recover to 95% capacity for internal battery@ 2A charging current
Charging Current
100/110/115/120 /127 VAC models: default 2A, max. 8A
adjustable
200/208/220/230/240 VAC models: default 2A, max. 12A
adjustable
Default: 2A, Max: 8A
adjustable
Charging Voltage
27.4 VDC ± 1%
41.0 VDC ± 1%
54.7 VDC ± 1%
82.1 VDC ±1%