04: ECO enable/disable
Interface
Setting
Parameter 2:
Enable or disable ECO function. You
may choose the following two options:
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)
05: ECO voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point
and low voltage point for ECO mode by pressing
Down key or Up key.
HLS:
High loss voltage in ECO mode in parameter
2.
For 200/208/220/230/240 VAC models, the setting
range in parameter 3 is from +7V to +24V of the
nominal voltage. (Default: +12V)
For 100/110/115/120/127 VAC models, the setting
range in parameter 3 is from +3V to +12V of the
nominal voltage.
(Default: +6V)
LLS:
Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting
range in parameter 3 is from -7V to -24V of the
nominal voltage.
(Default: -12V)
For 100/110/115/120/127 VAC models, the setting
voltage in parameter 3 is from -3V to -12V of the
nominal voltage.
(Default: -6V)
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 2:
Enable or disable Bypass function. You
may choose the following two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)