Chapter 5: Subsystem Maintenance
Cooling FAN Module Maintenance
5-11
5.
After the PSU module has been dislodged from the enclosure, use the handle at the
rear of the PSU to
gently pull the PSU module out of the enclosure
. (See
Figure
5-6
)
Figure 5-6:
Removing the PSU from the subsystem
6.
Once the faulty PSU has been removed,
insert the new PSU module
into the
subsystem. Push the PSU into the slot until it clicks into place.
7.
To firmly secure the PSUs into place, reinsert the retention screw.
8.
Replace the power cable that is used to connect the PSU module to the mains.
9.
Turn the PSU module on.
5.5. Cooling FAN Module Maintenance
5.5.1 Notes on Cooling FAN Module Maintenance
WARNING:
If the latches at the back of the cooling FAN module, which are used to secure the
cooling FAN module into the enclosure, are broken, the warranty on the cooling FAN
module will be void.