INSTRUCTION

SEZ2M24

IN20071 REV. A, 2022-04-04

Caution!

Read and understand the instruction before using the product.

Caution!

Ensure that the installation complies with local safety

regulations.

Caution!

Before installation or maintenance, the power supply should

first be disconnected. Installation or maintenance of this unit should only
be carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.

Function

The SEZ2M24 is an electromechanical actuator, intended for use in
applications such as heating, cooling, ventilation, chilled beams, fan-coils
and radiators. The actuator has DIP switches for setting different functions.
The actuator is very versatile, suitable for a wide range of valves.

Technical Data

Supply voltage

24 V AC/DC +/- 15 %

Control signal

0(2)…10 V / (0)4…20 mA

Power consumption

2 W / 6 VA

Inrush current

1.8 A

Stroke

1-8.5 mm

Running time

5.5 s / mm

Force

200 N

Visual position indicator

LED

Status and diagnostic indicator

LED

Manual override

By 4 mm Allen key

Ambient temperature

0…50 °C

Ambient humidity

95 % RH, non-condensing

Dimensions (W x H x L)

50 x 88 x 93 mm

Protection class

IP54

Cable length

1.5 m (halogen free)

Installation

Start-up sequence

When the power to the actuator is turned on, the actuator automatically
calibrates to determine closing point and stroke length of the valve. After
that it will proceed to normal operation according to control signal.

Note!

The actuator will not work properly if no valve is installed.

Mounting

Upside down installation is allowed, along with the standard horizontal and
vertical installation.

Fix the actuator to the valve using the connection nut, manual power is
sufficient.

Caution!

Do not use any tools as they can damage the actuator bracket.

Make sure the actuator stem is completely retracted before mounting it
on the valve.

Valves from other brands

See valve requirements in image below, when using valves from other
brands than Industrietechnik.

A

B

C

M30 x 1,5 mm*

D

Figure 1 A = min. 9.0 mm; B = max 17.5 mm; C = max Ø 20.5 mm; D = max 9.0
mm, * Adapters in range M28 x 1.5 mm to M30 x 1.5 mm are available. Contact
Industrietechnik for more information.

Wiring

The actuator has a halogen free connection cable fixed to the actuator.

Connect the supply voltage and control signal. If the actuator and controller
share a transformer, it is very important to keep the phase separate from the
zero, so the same pole is used as zero for both controller and actuator, since
this is the reference for the control signal.

1

2

3

4

24 V AC/DC (G) (+)

24 V AC/DC (G0) (-)

0…10 V DC input

0…10 V DC output

Figure 2 1 = Black; 2 = White; 3 = Red; 4 = Green

DIP switches

There are six DIP switches for setting different functions. Follow the table
below for setting the DIP switches.

Adjusted settings will be valid only after the next power-on.

Open the switch rubber seal with a screwdriver. Rotate the rubber seal
upwards to have access to the DIP switches. If switch setting is changed
during operation the power need to be cut and put back on before the
settings to take effect.

Note!

When the switch rubber seal is open, IP54 rating no longer applies.

SEZ2M24

1 (9)

Summary of Contents for SEZ2M24

Page 1: ...g to control signal Note The actuator will not work properly if no valve is installed Mounting Upside down installation is allowed along with the standard horizontal and vertical installation Fix the actuator to the valve using the connection nut manual power is sufficient Caution Do not use any tools as they can damage the actuator bracket Make sure the actuator stem is completely retracted befor...

Page 2: ...r acteristic curve Switch coding Characteristic curve for valve Characteristic curve for actuator Effective on valve Equal percentage Switch 2 Off Switch 5 On V A B A B V Linear Switch 2 On Switch 5 On V A B A lin B V Equal percentage Switch 2 Off Switch 5 Off V A B A B V Linear Switch 2 On Switch 5 Off V A B A lin B V A Stroke B Signal LED indication The actuator has two LED lights with indicatio...

Page 3: ...o di chiusura e la lunghezza della corsa della valvola Dopodiché funzionerà normalmente in base al segnale di comando Nota L attuatore non funzionerà correttamente se non viene installato sulla valvola Montaggio È consentita l installazione capovolta oltre all installazione standard orizzontale e verticale Fissare l attuatore alla valvola tramite la ghiera è sufficiente il serraggio a mano Attenzi...

Page 4: ...attuatore L interruttore 5 è la caratteristica di portata della valvola stessa Curva carat teristica desiderata Codifica interruttori Curva caratte ristica della valvola Curva caratte ristica dell attuatore Effettiva su valvola Equipercen tuale Inter 2 Off Inter 5 On V A B A B V Lineare Inter 2 On Inter 5 On V A B A lin B V Equipercen tuale Inter 2 Off Inter 5 Off V A B A B V Lineare Inter 2 On In...

Page 5: ...0 N Optische Stellungsanzeige LED Status und Diagnose Anzeige LED Handverstellung Mittels 4 mm Inbusschlüssel Umgebungstemperatur 0 50 C Umgebungsfeuchte 95 RH nicht kondensierend Maße B x H x L 50 x 88 x 93 mm Schutzart IP54 Kabellänge 1 5 m halogenfrei Installation Startsequenz Beim Einschalten führt der Stellantrieb automatisch eine Kalibrierung durch um den Schließpunkt und die Hublänge des Ve...

Page 6: ... Stellantrieb öffnet das Ventil bei steigendem Stellsignal On Umgekehrter Betrieb Der Stellantrieb schließt das Ventil bei steigendem Stellsignal SW4 Stellsignal Off 0 10 V DC On 2 10 V DC SW5 Ventildurchflusskennlinie Off Linear On Gleichprozentig Weitere Informationen unter Kennlinien SW6 Stellsigna Typ Off Spannung 0 2 10 V On Strom 0 4 20 mA Kennlinien Folgende Tabelle zeigt die Einstellungen ...

Page 7: ...sactivation des dispositifs de sécurité Fonctionnement Le SEZ 2M24 est un actionneur électromécanique destiné à être utilisé dans des applications telles que le chauffage le refroidissement la ventilation les poutres froides les ventilo convecteurs et les radiateurs L actionneur est doté de commutateurs DIP pour le réglage de différentes fonctions Il est particulièrement polyvalent et convient à u...

Page 8: ...trée 0 10 V 2 10 V 5 Clapet Linéaire Clapet Pourcentage égal 6 Entrée 0 10V DC 2 10V DC Entrée 0 20 mA 4 20 mA SW1 Sens de fonctionnement de la vanne Off La vanne est fermée lorsque la tige est tirée à fond c à d dans sa position la plus haute On La vanne est fermée lorsque la tige de la vanne est dans sa position la plus basse SW2 Caractéristique de débit souhaitée Off Caractéristiques de débit à...

Page 9: ...s 2 1 Tournez la clé Allen dans le sens des aiguilles d une montre pour allonger la tige de l actionneur Cela permet de fermer la vanne si elle se ferme lorsque la tige est poussée vers l intérieur Tournez la clé Allen dans le sens inverse des aiguilles d une montre pour rétracter la tige Ceci ouvre la vanne si la vanne elle se ferme lorsque la tige est rentrée Fig 3 Gauche La vanne est ouverte lo...

Reviews: