DIP switch settings

The actuator is delivered with factory setting as shown in the table below. All
switches are set to "Off", except switch 1.

Off

On

1

4

5

6

2

3

Off

On

1

Actuator stem retract to
close

Actuator stem extend to
close

2

Flow: Equal percentage

Flow: Linear

3

Direct action

Reverse action

4

0…10 V input

2…10 V input

5

Plug: Linear

Plug: Equal percentage

6

Input: 0…10V DC / 2…
10V DC

Input: 0…20 mA / 4…20
mA

SW1 Operational direction of the valve

Off: The valve is closed when the valve stem is in its highest position.
On: The valve is closed when the valve stem is in its lowest position.

SW2 Desired effective characteristic

Off: Effective equal percentage flow characteristics
On: Effective linear flow characteristics.
See more information under

Characteristic curves

.

SW3 Reverse/Direct operation

Off: Direct operation. The actuator opens the valve on increasing control
signal.
On: Reverse operation. The actuator closes the valve on increasing control
signal.

SW4 Control signal

Off: 0...10 V DC
On: 2...10 V DC

SW5 Valve flow characteristic

Off: Linear.

On: Equal percentage.
See more information under

Characteristic curves

.

SW6 Control signal, type

Off: Voltage 0 (2)-10 V
On: Current 0 (4)-20mA

Characteristic curves

The table below shows settings for switch 2 and switch 5. Switch 2 is the
desired effective function you want out of the valve and actuator
combination. Switch 5 is the flow characteristics of the valve itself.

Desired char-
acteristic
curve

Switch coding

Characteristic
curve for valve

Characteristic
curve for
actuator

Effective on
valve

Equal
percentage

Switch 2 = Off
Switch 5 = On

V

A

B

A

= %

B

V

Linear

Switch 2 = On
Switch 5 = On

V

A

B

A

lin

B

V

Equal
percentage

Switch 2 = Off
Switch 5 = Off

V

A

B

A

= %

B

V

Linear

Switch 2 = On
Switch 5 = Off

V

A

B

A

lin

B

V

A = Stroke; B = Signal

LED indication

The actuator has two LED lights with indications according to the table
below.

Green LED fixed light

Actuator moving, under operation

Green LED quick flash

Stroke adaption

Green LED slow flash (Flash twice +
Off 2 sec.)

0 % position

Green LED slow flash (Flash twice +
On 1 sec. + Off 1 sec.)

100 % position

Red LED lights

End of SWs fault / more than 2 faults

Red LED quick flash

One of End SWs fault

Red LED slow flash (Flash once + Off 2
sec.)

Settings changed during operation

Red LED slow flash (Flash twice + Off 2
sec.)

Auto stroke adapt fault

Manual override

To set the actuator to manual override, follow these steps:

1. Remove the manual override rubber seal with a screwdriver to have

access to the Allen key hole.

2. Use the 4 mm Allen key to turn the screw.

2

1

– Turn the Allen key

clockwise

to extend the actuator stem. This closes

the valve if the valve itself is closing when valve stem is pushed into the
valve.

– Turn the Allen key

counterclockwise

to retract the stem. This opens

the valve if the valve itself is closing when valve stem is pushed into the
valve.

Figure 3 Left: Valve is open when the valve stem is extended. Right: Valve is
closed when the valve stem is pushed into the valve.

Note!

If the valve opens when the valve stem is pushed in, the function is

the opposite.

SEZ2M24

2 (9)

Summary of Contents for SEZ2M24

Page 1: ...g to control signal Note The actuator will not work properly if no valve is installed Mounting Upside down installation is allowed along with the standard horizontal and vertical installation Fix the actuator to the valve using the connection nut manual power is sufficient Caution Do not use any tools as they can damage the actuator bracket Make sure the actuator stem is completely retracted befor...

Page 2: ...r acteristic curve Switch coding Characteristic curve for valve Characteristic curve for actuator Effective on valve Equal percentage Switch 2 Off Switch 5 On V A B A B V Linear Switch 2 On Switch 5 On V A B A lin B V Equal percentage Switch 2 Off Switch 5 Off V A B A B V Linear Switch 2 On Switch 5 Off V A B A lin B V A Stroke B Signal LED indication The actuator has two LED lights with indicatio...

Page 3: ...o di chiusura e la lunghezza della corsa della valvola Dopodiché funzionerà normalmente in base al segnale di comando Nota L attuatore non funzionerà correttamente se non viene installato sulla valvola Montaggio È consentita l installazione capovolta oltre all installazione standard orizzontale e verticale Fissare l attuatore alla valvola tramite la ghiera è sufficiente il serraggio a mano Attenzi...

Page 4: ...attuatore L interruttore 5 è la caratteristica di portata della valvola stessa Curva carat teristica desiderata Codifica interruttori Curva caratte ristica della valvola Curva caratte ristica dell attuatore Effettiva su valvola Equipercen tuale Inter 2 Off Inter 5 On V A B A B V Lineare Inter 2 On Inter 5 On V A B A lin B V Equipercen tuale Inter 2 Off Inter 5 Off V A B A B V Lineare Inter 2 On In...

Page 5: ...0 N Optische Stellungsanzeige LED Status und Diagnose Anzeige LED Handverstellung Mittels 4 mm Inbusschlüssel Umgebungstemperatur 0 50 C Umgebungsfeuchte 95 RH nicht kondensierend Maße B x H x L 50 x 88 x 93 mm Schutzart IP54 Kabellänge 1 5 m halogenfrei Installation Startsequenz Beim Einschalten führt der Stellantrieb automatisch eine Kalibrierung durch um den Schließpunkt und die Hublänge des Ve...

Page 6: ... Stellantrieb öffnet das Ventil bei steigendem Stellsignal On Umgekehrter Betrieb Der Stellantrieb schließt das Ventil bei steigendem Stellsignal SW4 Stellsignal Off 0 10 V DC On 2 10 V DC SW5 Ventildurchflusskennlinie Off Linear On Gleichprozentig Weitere Informationen unter Kennlinien SW6 Stellsigna Typ Off Spannung 0 2 10 V On Strom 0 4 20 mA Kennlinien Folgende Tabelle zeigt die Einstellungen ...

Page 7: ...sactivation des dispositifs de sécurité Fonctionnement Le SEZ 2M24 est un actionneur électromécanique destiné à être utilisé dans des applications telles que le chauffage le refroidissement la ventilation les poutres froides les ventilo convecteurs et les radiateurs L actionneur est doté de commutateurs DIP pour le réglage de différentes fonctions Il est particulièrement polyvalent et convient à u...

Page 8: ...trée 0 10 V 2 10 V 5 Clapet Linéaire Clapet Pourcentage égal 6 Entrée 0 10V DC 2 10V DC Entrée 0 20 mA 4 20 mA SW1 Sens de fonctionnement de la vanne Off La vanne est fermée lorsque la tige est tirée à fond c à d dans sa position la plus haute On La vanne est fermée lorsque la tige de la vanne est dans sa position la plus basse SW2 Caractéristique de débit souhaitée Off Caractéristiques de débit à...

Page 9: ...s 2 1 Tournez la clé Allen dans le sens des aiguilles d une montre pour allonger la tige de l actionneur Cela permet de fermer la vanne si elle se ferme lorsque la tige est poussée vers l intérieur Tournez la clé Allen dans le sens inverse des aiguilles d une montre pour rétracter la tige Ceci ouvre la vanne si la vanne elle se ferme lorsque la tige est rentrée Fig 3 Gauche La vanne est ouverte lo...

Reviews: